A cooling coil can only dry air down to about the temperature of its own fins. Take the fins below 0 °C and they frost instead of drying.
Condensing dehumidification works by cooling air below its dew point so water condenses on the coil. The leaving air can only get as dry as the coldest surface it touched. Once the fin surface is below freezing, moisture arrives as frost, which insulates the fins and chokes the air path. In practice a chilled-water coil stops several degrees above a freezing dew point.
A Li-ion dry room needs dew points far below that. Desiccant dehumidification uses a different mechanism: a rotor adsorbs water vapour from the process air and gives it up to a heated reactivation airstream. It keeps drying where a coil cannot, and Humiley's desiccant systems reach −60 °C dew point.
The design question is where one hands over to the other. The rotor is the expensive way to remove water, because reactivation heat is its running cost. So the usual train is a precooling coil ahead of the rotor to strip the bulk of the moisture from tropical outdoor air cheaply, the rotor for the deep drying, and a post-cooling coil to take away the heat the rotor adds.
Where that split sits, and how much outdoor air passes through the whole train, sets most of a dry room's energy bill.