"Laminar flow" is printed on the cabinet door. ISO 14644-1 never uses the word; its term is unidirectional airflow.
Laminar has a meaning in fluid mechanics: layers of fluid sliding past each other without mixing, which in a duct holds only up to a Reynolds number of about 2,300. Now take a clean zone at 0.45 m/s, the middle of the 0.36–0.54 m/s guidance range in EU GMP Annex 1, a zone 1 m across, and air at 20 °C with a kinematic viscosity near 0.000015 m²/s. Re = 0.45 × 1 ÷ 0.000015 = 30,000, more than ten times past the laminar limit.
What a HEPA ceiling delivers is something else, and it is enough: air leaving the filter face at a steady velocity, in streams that stay roughly parallel until they meet an obstacle. ISO 14644-1 defines unidirectional airflow in those terms. Annex 1 made the same change in 2022, and its glossary notes that a unidirectional airflow unit was "previously referred to as a Laminar Airflow Unit or LAF".
The word matters in a specification because nobody can test a room for laminar flow. The tests that exist are for the real requirement: air speed and its uniformity at the working position, and smoke studies showing the air moving one way past the product. Annex 1 says the visualization studies should correlate with the air speed measurement.
Does your URS still ask for laminar flow?