Draw an airlock into Grade B as a corridor with two doors and it often gets a transfer grille and leftover air.
That leftover is whatever remains once the process rooms are balanced. EU GMP Annex 1 (2022) asks for more: in its premises section it says, in paraphrase, that the final stage of an airlock should be the same grade at rest as the cleanroom it leads into. For a Grade B room that means ISO 5 at rest: no more than 3,520 particles of 0.5 µm and larger per m³.
Treated as a Grade B room in its own right, that last stage needs:
- terminal HEPA supply, with enough air to bring the count back down after the door opens and a gowned operator steps through;
- its own step in the pressure cascade, typically 10 to 15 Pa against the stage before it;
- a place in the environmental monitoring program, with particle counts and pressure logged like the other Grade B rooms.
Built the corridor way, the stage tends to count closer to Grade C at rest, and the Grade B room behind it takes in the difference each time someone walks through.
On a room data sheet this is easy to write down early: give each airlock stage its own line, with grade, air change rate and pressure, the same as a process room.