5% duct leakage into a hot void costs 3.4 kW

When 5% of a 10,000 m³/h, 12 °C supply leaks into a 32 °C ceiling void, about 3.4 kW of sensible cooling goes with it and the room is 500 m³/h short. A named airtightness class, a pressure test before insulation and sealed joints and access doors keep that cooling in the duct.

InsightRead

Cleanroom setback: timer or particle counts

A timed airflow setback is simple to validate but blind to off-schedule activity. Particle-count-driven airflow follows real use and can save more, but counters and their failure modes join the validated system. Either way, the room must recover to its at-rest limits, pressures stable, before operations restart.

InsightRead

A desk check for the airflow diagram

An airflow diagram shows every room's supply, return and exhaust on one sheet. For each room, supply minus return minus exhaust must leave a leakage that matches the pressure cascade, and the room flows must add up at each AHU. Five checks at the desk find errors that otherwise appear during balancing.