A tropical shower can drop outdoor air from 32 °C to about 26 °C while it still holds around 21 g/kg. The fresh-air coil loses sensible duty but keeps all its latent duty, and the room's own heat does not change. A single coil on temperature control closes and room RH climbs.
In a staged system only the fresh air is drier than the room. With 220 W of latent gain and 300 L/s of fresh air it must arrive about 0.24 g/kg drier; at 150 L/s, 0.49 g/kg. Check humidity before cutting outdoor air for energy.
A room at 24 °C and 55% RH reads about 62% RH at 22 °C if no water is removed, because the dew point has not moved. On most cleanroom air handling units a lower setpoint only cuts reheat. Compare supply air dew point with room dew point before changing anything.
Reheat lowers the RH reading and leaves the water in the air. Before adding it, check outdoor dew point against design, chilled water temperature and valve position, and coil leaving dew point. Then look at reheat and the room sensor, and finally at doors, infiltration and new moisture sources.
An ISO 8573-1:2010 class such as [1:2:1] is three limits in a fixed order: particles, water as pressure dew point, and total oil. Class 2 water is −40 °C or lower; class 1 oil is 0.01 mg/m³ or less. The class does not name a location, so state the point of use.
Below 0 °C, moisture in air can be stated as a dew point over supercooled water or a frost point over ice, and the frost point is the warmer number. At a frost point of −40 °C the dew point is about −43.7 °C. A dry-room specification should say which one it means.
Some reheat is the price of dehumidification; the rest is waste. Five BMS trends separate the two: cooling and reheat valve positions together, supply dew point against what the rooms need, overlapping setpoints, temperature change across a coil with its valve shut, and the same pattern at night and weekends.
A chilled-water reset driven by valve position alone can raise supply water by 2 K, save chiller energy in the dry season and leave dehumidifying coils unable to reach the dew point in the wet season. Lock the reset out on outdoor or supply-air dew point, retest it in the wet season and list the dehumidifying coils first.