Skip to content

Newsroom

News & Insights

Company news from Humiley Group INC and technical notes on cleanroom HVAC, GMP validation, semiconductor environments and energy-storage engineering.

  • 780 articles

Life Sciences

Life Sciences

17 articles tagged #DataIntegrity.

PIC/S PI 041-1 expects system administrator rights to sit apart from people who generate or approve GMP data, where possible. On small sites one engineer often does both. The conflict can be controlled: named separate accounts, admin activity reviewed by QA or IT, and configuration changes through change control.

InsightRead

What a printed EMS trend leaves out

FDA's 2018 data integrity Q&A separates static records from dynamic ones. A printed EMS trend keeps one view and leaves raw values, metadata and the audit trail behind. Keep the electronic original for the retention period, have the reviewer work in the system, and label printouts as convenience copies.

InsightRead

Infrastructure qualification under a GMP SCADA

Servers, network, virtualisation, backup and time sync under a GMP system are qualified as a controlled platform; the application on top is validated for its intended use. With the platform qualified, a routine OS patch needs an impact assessment and a targeted check, not a new OQ of the SCADA.

InsightRead

What an audit trail review actually looks for

Annex 11 asks for audit trails to be regularly reviewed but gives no list. On an EMS or BMS, filter for deleted data, setpoint and alarm limit changes outside change control, alarms acknowledged without comment, repeated tests before a pass, and clock or role changes. Then a reviewer can sign for it.

InsightRead

21 CFR 11.10(e) requires secure, computer-generated, time-stamped audit trails. For an environmental monitoring system, that means the software logs setpoint, alarm-limit and user changes itself, nobody can purge entries, every clock follows one time source, and the requirements sit in the URS before a platform is chosen.

InsightRead

GAMP 5 Second Edition (2022) scales validation effort to risk to patient safety, product quality and data integrity, and adds agile and cloud guidance. On a GMP BMS, test alarms, audit trail and data transfer deeply. A quick check: count low-risk functions that still carry full test scripts.

InsightRead

ALCOA+ on a paper pressure log

A paper room-pressure log with every reading in the same pen at the end of the shift fails ALCOA+ before any number is checked. Walking one sheet against the nine attributes, from attributable initials to enduring ink, shows that most data-integrity failures are fixed by redesigning the form.

InsightRead

A true copy is a copy of an original record that has been verified, by a dated signature or a validated process, to hold the same information, including context, content and structure. The MHRA guidance of 2018 says it may be retained in place of the original if a documented system is in place to verify and record the integrity of the copy.

InsightRead

The 2011 text of EU GMP Annex 11 (clause 6) says that where critical data are entered manually there should be an additional check on their accuracy, by a second operator or by validated electronic means. For a BMS or EMS alarm limit, a permitted range on the field and a confirmation step are the practical answer.

InsightRead

A stored value of 22.4 means nothing without its sensor tag, unit, time stamp, status flag, author and audit trail. The MHRA's 2018 data integrity guidance defines metadata as data that describe the attributes of other data and provide context and meaning. Test that backups, exports and migrations carry them.

InsightRead