The validation team arrives with an aerosol generator and a photometer.
The terminal HEPA housing has no upstream injection point and no way to sample the upstream concentration.
At that point the installed leak test cannot be done properly, and a filter that passed at the factory cannot be shown to be leak-free where it matters: in the ceiling.
The test itself is simple, and ISO 14644-3 describes it. Challenge the filter with aerosol upstream, measure the upstream concentration, then scan the whole downstream face and the perimeter seal with a probe. With a photometer, a reading above 0.01% of the upstream concentration is commonly treated as a leak.
Three details on the housing decide whether that is possible:
- An upstream aerosol injection point and an upstream sample port, reachable without dismantling the ceiling.
- A seal that can be scanned: a knife edge in gel, or a clamped gasket, with the frame joint exposed to the probe.
- A diffuser or grille that comes off without disturbing the filter.
Leaks at the frame and seal are a frequent finding, so a housing that hides the seal hides one of the most likely failures.
Specify terminal housings from the test backwards: if it cannot be scanned, keep it off the drawing.