Grade B at rest allows 29 particles of 5 µm and larger per m³. In operation the same room may hold 2,930.
At 0.5 µm the step is the same factor of 100: 3,520 per m³ at rest, equal to the Grade A limit at that size, against 352,000 in operation. For a RABS background room the at-rest figure is the one the design has to beat.
ISO 14644-1 leaves the at-rest equipment condition to agreement between customer and supplier. For GMP grades, Annex 1 (2022) is more specific: utilities complete with the HVAC running, the main manufacturing equipment installed as specified and standing by for operation, and no personnel present. The at-rest limits should be met after a short clean-up period following operations, with a guidance value of under 20 minutes.
That rules out some convenient set-ups. A room classified with the line isolated and its RABS fans switched off is not at rest in the Annex 1 sense. A reading taken an hour after the operators left shows the room at its cleanest, not that it gets there within the clean-up period.
The 5 µm channel shows the difference first. If that count sits near 29 with the line on standby, it is better found at qualification than after the first media fill.
The protocol should state the equipment condition and the time since the last person left. Commissioning and qualification are part of Humiley's project management work.