With a clean-air delivery rate of 300 m³/h, a portable HEPA unit gives a 60 m³ single room 5 equivalent air changes an hour.
That holds at the speed the rate was measured at, and the division is the useful way to judge one for a haematology ward. The clean-air delivery rate (CADR) is measured on the whole unit in a test chamber, so it already includes the filter's efficiency and any air that leaks round the filter inside the cabinet. Catalogue airflow includes neither. Divide CADR by the room volume and you get a figure the infection control team can set beside the air changes the central system provides.
Two checks change the answer. The first is speed. The rated CADR is usually at the top setting, and on a ward at night the unit gets turned down or off because of the noise. Ask for CADR at the setting that will be used. The second is placement. A unit in the corner behind the bed curtain cleans the corner. Air has to travel from its outlet across the patient's zone and back to its inlet.
A room unit only recirculates. It does not pressurise the room, does not replace filtered supply air, and cannot stop corridor air coming under the door. In a protective isolation room it supplements the positive pressure and filtered supply the guidance asks for.
Humiley engineers hospital clean zones with pressurisation treated as infection control.
What air change figure does your ward use when it compares room units?