An exhaust fan at the end of the run keeps every duct joint before it under negative pressure, so a leak draws air in, not dust out.
In a potent-compound suite the HEPA housing gets most of the attention. The fan and stack decide what happens to anything that passes the filter, and to the room when the fan stops.
- Fan position. At the end of the run, ideally on the roof or outside the occupied building. A fan halfway along puts its discharge duct under positive pressure inside the building.
- Redundancy. For a room that must stay negative, one fan is a single point of failure. Duty and standby fans with automatic changeover on a flow or pressure signal, each with an isolation damper so air does not short-circuit through the stopped one, and an alarm on every changeover.
- Stack height and exit velocity. A vertical discharge, high and fast enough to clear the building's wake, with no rain cap turning the plume back down. The values come from a standard or a dispersion study.
- Distance from intakes. Fresh-air intakes, a neighbour's included, kept upwind of the stack in the prevailing wind. A plume that re-enters through an AHU intake has bypassed every barrier in the building.
Then decide and test what the room does on a total power loss.