Heat recovery in a GMP unit: which way does a leak run?

  • Manufacturing & Distribution
  • 1 min read

Turning continuously through the exhaust and the supply, a thermal wheel carries some exhaust air round with it.

That carryover is part of how a wheel works. A purge sector cuts it down and the seals limit the rest, but neither brings it to zero. For a general area it can be accepted with a risk assessment. For exhaust from a potent-compound or containment suite, few QA heads will sign it.

A run-around coil sits at the other end. The two streams stay in separate casings and heat moves through a pumped glycol loop, so there is no shared air path to argue about. Recovery is lower and there is a pump to maintain, but the supply and exhaust ducts never have to meet.

The plate exchanger is the one most often got wrong. Its plates rarely leak much. What decides which way a leak runs is the pressure on each side, and the fan positions set that. With the supply fan downstream of the exchanger, drawing air through it, and the exhaust fan upstream, blowing through it, the exhaust side ends up at the higher pressure and any leak goes into the supply.

Two checks catch it. Mark the fan positions and the static pressure on each side of the exchanger on the schematic before the unit is ordered. Then measure both pressures at commissioning and file the readings.

We compare recovery options inside the energy model at design stage, which targets 30% lower HVAC energy.

Where does your QA draw the line for wheels?