A cascade drawing copied from a sterile suite into a high-potency OSD suite puts every door arrow in the wrong direction.
A sterile room is positive to its corridor because the product is what needs protecting. In a potent-compound compression or granulation room, the operator and the rest of the building need protecting from the product, so air has to move towards the powder. Drawn from the sterile template, every door opening pushes API dust into the corridor, and the pressure alarm stays green because the room does exactly what it was drawn to do.
The sterile layout is often the one a team has drawn most, and its template travels with the room data sheets.
Three checks on the drawing before it is issued:
- Follow the arrow at every door of the potent room. It should point into the room or into its airlock, never out to the corridor.
- Look at what the airlock does. A sink airlock, lower than both sides, takes air from both and extracts it. A bubble, higher than both, pushes clean air both ways where the product needs protecting too. Either works if it was chosen on purpose.
- Check the extract route. Air leaving a potent room carries powder, so its HEPA housing should allow a bag-in/bag-out filter change.
Which of the three do design reviews miss most often on your projects?