High-potency suites: a copied sterile cascade points the wrong way

  • Life Sciences
  • 1 min read

A cascade drawing copied from a sterile suite into a high-potency OSD suite puts every door arrow in the wrong direction.

A sterile room is positive to its corridor because the product is what needs protecting. In a potent-compound compression or granulation room, the operator and the rest of the building need protecting from the product, so air has to move towards the powder. Drawn from the sterile template, every door opening pushes API dust into the corridor, and the pressure alarm stays green because the room does exactly what it was drawn to do.

The sterile layout is often the one a team has drawn most, and its template travels with the room data sheets.

Three checks on the drawing before it is issued:

  1. Follow the arrow at every door of the potent room. It should point into the room or into its airlock, never out to the corridor.
  2. Look at what the airlock does. A sink airlock, lower than both sides, takes air from both and extracts it. A bubble, higher than both, pushes clean air both ways where the product needs protecting too. Either works if it was chosen on purpose.
  3. Check the extract route. Air leaving a potent room carries powder, so its HEPA housing should allow a bag-in/bag-out filter change.

Which of the three do design reviews miss most often on your projects?

Industries

Related

More on this subject

ISO Class 1 vs ISO 5: counting at 0.1 µm

ISO Class 1 allows 10 particles of 0.1 µm and larger per cubic metre; ISO 5 allows 100,000 at that size. At that level the installed leak scan must prove frames and grid, not just the U15 filter, single-digit counts need large sample volumes, and airborne molecular contamination needs its own sampling plan.

InsightRead

Maintenance that keeps the validated state

A filter changed on night shift without a leak test turns maintenance into a deviation. GMP maintenance works from criticality bands built on the asset register, planned and corrective work in one system, risk-based requalification and calibration, and 24/7 response across Southeast Asia under a maintenance agreement.

InsightRead

Three APS runs across all shifts, and the HVAC has to hold still

Annex 1 initial validation of an aseptic process needs at least 3 consecutive successful simulations covering all working shifts, then periodic runs twice a year per process, line and shift. The cleanroom must hold its qualified state throughout. Agree an HVAC freeze date with QA, and list in advance which jobs are like-for-like and which need an impact assessment.

InsightRead