Sized for the average draw, a purified water loop stagnates on the morning every use point opens at once.
A loop is meant to keep water moving everywhere, all the time. When several outlets draw together, the flow reaching the return leg drops, and on an undersized loop it can fall close to zero. The far end, the section nobody walks past, is where the water stands.
Turbulence is the usual target and the physics is short. Pipe flow is turbulent when the Reynolds number is above about 4,000. Re = v × D / ν, and for water at 20 °C, ν is about 1.0 × 10⁻⁶ m²/s. In a 22 mm bore at 0.1 m/s that gives Re ≈ 2,200. Laminar flow, in the pipe you most want scoured. At 1 m/s, a return velocity many designers use as a floor, the same pipe gives about 22,000.
What we check on a new loop design:
- The realistic maximum simultaneous draw, taken from the production schedule rather than the sum of all outlets or the daily average.
- Return flow at that draw, with the pump at its duty point.
- A flow meter on the return leg, trended in the BMS or SCADA.
- An alarm set above the flow that keeps the return turbulent, with a short delay so a brief dip does not bury the operators in alarms.
The alarm limit is often left blank at handover. Work it out from the return pipe size and the loop temperature, and write it into the URS.