Skip to content

News

When a capacitor bank resonates at the 7th harmonic

  • News
  • 1 min read

A 400 kvar capacitor bank on a bus with a 20 MVA fault level resonates close to the 7th harmonic, one of the orders an EC fan wall produces.

The capacitors and the supply's short-circuit inductance form a parallel resonance. Its order is roughly h = √(Ssc / Qc). With Ssc = 20 MVA and Qc = 400 kvar, h = √(20,000 / 400) = 7.07.

At that order the bus looks like a high impedance to harmonic current. The 7th-harmonic current from the drives pushes into it and the voltage distortion is amplified. The capacitor bank usually shows it first: fuses that blow, cans that run hot, a controller tripping for no clear reason.

Two things make it hard to catch. Automatic power factor correction switches steps in and out, so the resonance moves. With 200 kvar in service the same bus resonates at h = 10, clear of trouble; at the full 400 kvar it sits on the 7th. And on generator the fault level drops, so the resonance slides lower, towards the 5th.

A six-pulse rectifier front end produces the 5th, 7th, 11th and 13th. EC fan walls reach THDi of 35–42% with DC chokes and 65–75% without.

On EC fan walls we ask for harmonic data, specify DC chokes and decide on active filtering from a study, targeting THDi ≤ 5% at the point of common coupling (our design figure; IEEE 519-2022 limits TDD). A detuned reactor on each capacitor step is part of the same conversation.

Has anyone worked out the resonant order of your capacitor bank at every step?

Related

More on this subject

When an engineering gap is actually closed

A gap marked closed needs evidence someone else can check: a revised drawing and calculation for a design gap, the same test repeated for a performance gap, an effective SOP with training records for a procedural gap. Agree the evidence before the work starts, and have someone other than the fixer sign it.

InsightRead