Where the dossier describes rooms, flows and equipment

  • Life Sciences
  • 1 min read

For a biotech product, one section of the dossier describes rooms, flows and equipment.

It is the appendix on facilities and equipment, section 3.2.A.1 of ICH M4Q(R1), and under the heading "Biotech" it asks for things a facility engineer normally keeps on the drawing board.

A diagram should be provided illustrating the manufacturing flow, including the movement of raw materials, personnel, waste and intermediates. Information should be presented on adjacent areas or rooms that may be of concern for maintaining the integrity of the product, and on all developmental or approved products manufactured or manipulated in the same areas.

For equipment, the section says a summary description of product-contact equipment and its use, dedicated or multi-use, should be provided. Information should also be included on procedures, such as cleaning and production scheduling, and on design features of the facility, such as area classifications, to prevent contamination or cross-contamination.

Read that list beside a layout. The flow diagram is the personnel, material and waste flow drawing, and the adjacent areas come off the zoning plan and the pressure cascade. Dedicated or multi-use was decided at URS stage. Each is settled early in design and later becomes a statement to a regulator, so the dossier writer needs the drawings at the revision that was built.

Industries

Related

More on this subject

Zoning and Pressure Cascade

In pharmaceutical facility design, if the HVAC system is the "lungs," then the Zoning and Pressure Cascade strategy is the "immune system." It creates invisible but effective barriers that prevent microbial ingress and strictly control…

InsightRead

Energy savings and the requalification bill

Energy measures that change validated cleanroom conditions go through Annex 15 change control. Classification alone can mean 10 sample locations for a 50 m² room, at rest and in operation, before recovery tests and a CCS update. Price that next to the kWh, or design reduced modes in and qualify them once.

InsightRead

EU GMP Chapter 3 and 21 CFR 211 on HVAC

21 CFR 211.42 and 211.46 and EU GMP Chapter 3 ask for adequate ventilation, air control and filtration, but give no air change rate or pressure differential, and no filter class beyond HEPA for aseptic areas. Those come from Annex 1, FDA's 2004 aseptic guidance, ISO 14644 and the designer's justification, recorded in the design basis.

InsightRead