A capture hood throttles the terminal it measures and assumes an even flow across its sensing grid, so on a swirl diffuser it can read well off the true airflow, in either direction. Name the method per terminal type in the protocol, use back-pressure compensation, and check the hood against a duct traverse.
EU GMP Annex 1 (2022) asks for an integrity test of final filters at requalification and puts no age on the filter. A terminal HEPA is replaced when a leak cannot be repaired within site limits, when pressure drop reaches the manufacturer's final value, or after damage or wetting. On glass-fibre media, dust loading alone does not lower efficiency.
Replacing one failed terminal HEPA in a live Grade C suite starts with change control and an equivalent filter. Stop work, bag the old filter, inspect the housing, then fit and leak-scan the new filter in place. Clean and check airflow, pressures, counts and recovery before release, with the scope agreed in the change record.
The 1999 edition of ISO 14644-1 asked for a 95% upper confidence limit when a room had two to nine sampling locations. The 2015 edition removed it: the number of locations comes from Table A.1 and each location's average has to meet the class limit. Protocols that still carry the formula mix two methods.
The ISO 14644-3 installed leak test needs an upstream aerosol injection point, an upstream sample port and a perimeter seal the probe can reach. With a photometer, above 0.01% of upstream concentration is commonly treated as a leak. Specify terminal housings from the test backwards.
EU GMP grades map to different ISO 14644-1 classes at rest and in operation: Grade B is ISO 5 at rest and ISO 7 in operation. A URS line that quotes only one invites the wrong design. State both classes, the maximum number of people and the clean-up period.
ACH is supply airflow divided by room volume: 2,400 m³/h in a 120 m³ room is 20 ACH. It is an output of the class, heat load and 100:1 recovery time the room needs. Write those into the URS, keep ACH as a check, and prove the room with particle counts and a recovery test.