Why a capture hood can misread a swirl diffuser

  • News
  • 1 min read

12% short of design airflow by the capture hood, on design by the duct traverse. The hood was sitting on a swirl diffuser.

Both instruments were in calibration. A capture hood is calibrated on an even, straight flow, and on a real terminal it disturbs what it measures in two ways. Its resistance throttles the outlet while it sits there. Its sensing grid expects the air to fill the hood evenly, and a swirl diffuser throws a rotating jet along the hood wall instead. The error can go either way. One hood maker's note puts it at up to 40% of flow and beyond on swirl diffusers without a flow conditioner. The 12% is an illustration.

Hood makers supply the tools: a back-pressure compensation routine, and correction factors or conditioners for particular outlets. They are in the manual and rarely in the balancing procedure.

The fix is a line in the protocol. Name the method and instrument for each terminal type; ISO 14644-3 gives its test methods in outline and expects them to be agreed between customer and supplier. Then check the hood once against a duct traverse for each terminal type and record the factor.

Without that factor on file, the next gap between hood and traverse turns into an argument about instruments.

Related

More on this subject

Both states are required; only the stage is a choice

A 50 m² Grade B room needs 10 classification locations under ISO 14644-1:2015, and EU GMP Annex 1 requires them at rest against ISO 5 and in operation against ISO 7, with the smoke study in both states. Whether each run sits in OQ or PQ is for the URS and risk assessment to justify.

InsightRead

Set a device assembly room's class from the product's risk

ISO 13485 §6.4.2 asks for documented contamination control without naming a cleanroom class. Setting the class from sterilisation method, patient contact and bioburden sensitivity often lands device assembly at ISO 8, with ISO 7 only where needed, less air than Grade C, a smaller AHU and a reason an auditor can read.

InsightRead

Energy savings and the requalification bill

Energy measures that change validated cleanroom conditions go through Annex 15 change control. Classification alone can mean 10 sample locations for a 50 m² room, at rest and in operation, before recovery tests and a CCS update. Price that next to the kWh, or design reduced modes in and qualify them once.

InsightRead