The cube law says a fan at 50% airflow needs 1/8 of its full-flow power. The motor behind it was never rated at that point.
That 1/8 is power into the impeller, and it assumes the fan keeps its efficiency. The meter also sees motor and drive losses. At the setback point the motor turns at half speed and delivers about 25% of its rated torque, and many setback business cases still apply the nameplate efficiency there. The saving comes out larger than the one the meter later records.
With an induction motor on a VFD, ask for two figures: the motor's losses at light load and the drive's own. IEC 61800-9-2 sets out how to state power drive system losses at part-load operating points, including 50% speed and 25% torque, so a supplier can give a number instead of a full-load curve.
An EC fan has a permanent-magnet motor with the electronics built in, and the maker tests fan, motor and controller as one unit. It usually holds up better at low speed. Regulation (EU) 2024/1834 still sets the fan's minimum efficiency at its best point, but the datasheet must now give part-load information. Ask for it at the setback duty point: input kW at that airflow and pressure.
Put the setback duty point on the fan schedule next to the design point, with input kW for each. Our energy modeling targets a 30% cut in HVAC energy, and setback only counts toward it once that line exists.
Which duty points does your fan schedule list today?
Topics




