Under USP <800>, rooms for compounding hazardous drugs are held 2.5 to 7.5 Pa negative to their neighbours. The whole window is 5 Pa.
Cytotoxics are among the hazardous drugs it covers, and it gives the pressure in inches. The containment room must be at a negative pressure between 0.01 and 0.03 inches of water column relative to all adjacent areas. One inch of water is about 249 Pa, which gives roughly 2.5 to 7.5 Pa. The room must also be externally vented, with at least 12 or 30 air changes per hour depending on the type of room.
USP <800> is a US standard; local hospital-pharmacy rules decide what applies on a site in Viet Nam.
A cascade step between cleanroom grades in a pharmaceutical plant is typically 10 to 15 Pa. Here the pressure has an upper limit, and it sits below that range.
The lower limit is containment: air moves into the room, so drug particles and vapours stay in. For the upper limit we can only give our own reading. Where the room is also an ISO Class 7 buffer room for sterile work, pulling it harder draws unfiltered air through the door frame, the ceiling and every service penetration.
So the transmitter has to resolve single pascals, and the room has to be tight, because the leaks are where unfiltered air gets in.