Skip to content

Newsroom

News & Insights

Company news from Humiley Group INC and technical notes on cleanroom HVAC, GMP validation, semiconductor environments and energy-storage engineering.

  • 780 articles

Life Sciences

Life Sciences

26 articles tagged #Automation.

When the SCADA admin also runs the shift

PIC/S PI 041-1 expects system administrator rights to sit apart from people who generate or approve GMP data, where possible. On small sites one engineer often does both. The conflict can be controlled: named separate accounts, admin activity reviewed by QA or IT, and configuration changes through change control.

InsightRead

Part 11 applies to electronic records that a predicate rule such as 21 CFR 211 requires. For a BMS or EMS, name the rule behind each point: GMP-critical monitoring usually belongs in a validated EMS. For EU export, Annex 11 has no predicate-rule test, so the BMS still needs a risk assessment.

InsightRead

Infrastructure qualification under a GMP SCADA

Servers, network, virtualisation, backup and time sync under a GMP system are qualified as a controlled platform; the application on top is validated for its intended use. With the platform qualified, a routine OS patch needs an impact assessment and a targeted check, not a new OQ of the SCADA.

InsightRead

Backup and archive are two controls under Annex 11

EU GMP Annex 11 clause 7.2 asks for regular backups whose restore is checked during validation and periodically. Clause 17 asks that archived data stays accessible, readable and intact, with retrieval re-tested after system changes. A green nightly backup does not prove that old trend data opens after an upgrade.

InsightRead

GAMP 5 Second Edition (2022) scales validation effort to risk to patient safety, product quality and data integrity, and adds agile and cloud guidance. On a GMP BMS, test alarms, audit trail and data transfer deeply. A quick check: count low-risk functions that still carry full test scripts.

InsightRead

ALCOA+ on a paper pressure log

A paper room-pressure log with every reading in the same pen at the end of the shift fails ALCOA+ before any number is checked. Walking one sheet against the nine attributes, from attributable initials to enduring ink, shows that most data-integrity failures are fixed by redesigning the form.

InsightRead

E-signatures: the second signing is the test

21 CFR 11.200(a)(1) requires two distinct identification components for non-biometric signatures. Later signings in one continuous session must still use a component only the signer can execute, usually the password. Define the session and its timeout in writing, then test both cases at OQ.

InsightRead

Individual logins make records attributable, but user lists drift as people move and leave. A periodic access review exports users and roles from the system, checks them against HR's leavers and movers, justifies every admin or generic account and is signed with its corrections, the record an inspector will ask for.

InsightRead

Keep the BMS outside the EMS validation boundary

When the BMS and the validated EMS share one platform, the validation boundary takes in the control logic and every setpoint change becomes change control. An EMS with its own sensors, database and QA alarms under Part 11 and Annex 11 allows the BMS to be managed under good engineering practice.

InsightRead

21 CFR 11.100 sets three general requirements for electronic signatures: each one unique to one individual and never reassigned, identity verified before a signature is assigned, and a certification to FDA that the signatures are the legally binding equivalent of handwritten ones. All three belong in the URS and the site procedure.

InsightRead

21 CFR Part 11 and EU GMP Annex 11 overlap on validation, access control and audit trails but differ in emphasis: Part 11 on electronic signatures, Annex 11 on a risk-based system lifecycle. Fixing the destination market in the design basis means the URS and validation plan for BMS, EMS and SCADA are written once.

Read