Humidity control usually fails on a mild, saturated night at low occupancy: little sensible load, full latent load from the fresh air. A coil controlled on temperature throttles back and RH climbs. Run the case, control the coil on leaving dew point and size reheat for it.
Plot outdoor, mixed, coil-leaving, after-fan, after-reheat and room states on one psychrometric chart. A reviewer can see a mixed-air point off its line, a coil dew point without margin for the room latent load, over-drying paid for twice, and reheat oversized because fan heat was ignored.
On chilled-water pipes in a humid plant room, insulation is sized to keep the outer surface above the ambient dew point. BS 5422 and ISO 12241 take water temperature, air temperature, dew point and cladding emissivity. The vapour barrier then has to run unbroken through every hanger, valve and flange.
A low leaving dew point can come from a deeper coil with warmer water or a compact coil with colder water. The first costs fan pressure every running hour; the second costs chiller COP, about 3% per kelvin in an ideal cycle. The cheaper option depends on hours, tariff and how much of the plant shares the water.
When a DX compressor cycles off and the fan keeps running, the water film left on the coil re-evaporates into the supply air, so net dehumidification falls short of the rating at part load. Cleanrooms cannot cycle their fans, so they need modulating or staged capacity, or chilled water.
Heating 18 °C, 60% RH air to 22 °C drops the reading to about 47% RH while the air keeps 7.7 g of water per kilogram. A room that meets RH only on reheat has no margin for one fault. Trend reheat output beside room RH: rising reheat means the coil is losing latent capacity.
Cartons and labels from an 80% RH warehouse release moisture in a 20% RH packing room. If board gives up 2% of its weight, a 500 kg delivery adds 10 kg of water. Stage packaging in a controlled area, unwrapped, for a time set by weighing sample cartons.
Air leaving a coil at 12 °C and 95% RH reads about 50% RH at 22 °C with the same 8.3 g/kg of water. A duct RH sensor after the coil works at the top of its scale. Control the coil on dew point or leaving-air temperature, and keep duct RH after reheat as a wet-filter alarm.
A 100 cm² door gap at 15 Pa passes about 110 m³/h, but only doors on the suite boundary cost fresh air. Internal door leakage returns through the neighbouring room's grille. For twenty doors with four on the boundary, the leakage to make up is 440 m³/h rather than 2,200 m³/h of wet tropical air.
Light office wear is about 0.5 clo, while full cleanroom gowning sits nearer 1.0 clo, and standing line work is about 1.6 met or more. Gowned operators are comfortable cooler than office staff, so set the room temperature in the URS with QA and EHS before the load calculation sizes the coil.
When cooling and reheat valves open together at 20 ± 0.5 °C, the cause is usually a zero gap between the two control sequences. Check the trend first. Where the product data supports 20 ± 2 °C, cooling above 21 °C and reheat below 19 °C let the room drift between with both valves shut.
Ten per cent on the load, on the airflow and on the coil multiplies to 1.33, because each margin sits on the one before. The oversized coil runs at part load most of the year, condenses less water, and RH climbs while temperature holds. One named margin and a part-load check avoid it.