Duct leakage, cascade balance, controls tuning and recovery can only be measured once an AHU is connected on site. A FAT can still speed up those tests by recording clean filter and coil pressure drops, the casing leakage result, fan airflow at design static and the panel software version with its I/O list.
Substitutions reach site through vendor drawings approved in a hurry. Before releasing fabrication, check the duty point at design conditions, materials in the air path, clearances against the BIM model, sensors against the BMS I/O list, and the certificates and FAT procedure that must come with the unit.
Taking one AHU out of a running GMP plant changes the leakage balance of the rooms next door, and a 10 Pa step between grades can fall away. Seal shared air paths first, trim return dampers on the boundary rooms, record their original positions and keep EMS alarm limits at validated values.
In a ceiling of forty fan filter units, a stopped one looks like a running one. Most EC-driven FFUs can report their status. Send each fault to the BMS or SCADA for a time-stamped record, and add a local indication at the room so the operator sees it before a batch starts.
Clean AHU cooling coils from the leaving face with low-pressure water or steam and an approved, fully rinsed detergent, after checking the drain. Take the frequency from the coil's pressure drop trend against a commissioning baseline, and record the method, detergent batch, before and after readings and photos of both faces.
Airlock door interlocks protect a 10–15 Pa step between grades; a fire needs the doors to open. Specify both together: interlock logic, status lamps, fire-alarm release, fail-safe locks, a logged BMS alarm on every override, and a release tested at FAT, at OQ and periodically.
Filter transmitters get bought twice, or not at all, when the tender never says who supplies them. An AHU/BMS interface schedule lists every sensor, drive signal, actuator and fire alarm contact with who supplies, mounts, wires and configures it, attached to both tenders before they go out.
A pre-filter changed at 150 Pa on a 0–1,000 Pa gauge sits in the bottom 15% of the dial with about 20 Pa of uncertainty. A 0–250 Pa gauge puts it at 60% with 5 Pa. Range each stage's gauge and transmitter to its own change point.
When a supply AHU trips with extract fans running and dampers open, a Grade B room loses its 10–15 Pa margin and pulls air from the lower grade. Tight-shutoff dampers with a tested leakage class, defined fail positions, interlocks, proven position and a supply-first restart keep the cascade, and a deliberate fan trip at FAT proves it.
A fixed-speed fan filter unit loses airflow as its HEPA filter loads. Set at 0.45 m/s, it has 20% to lose before the 0.36 m/s bottom of the Annex 1 guidance range. Constant-airflow EC units hold velocity if they are selected at the final pressure drop, and their speed trend doubles as a filter-loading record.
A locked isolator does not stop a fan that windmills in the draught from a neighbouring unit. Isolating an AHU means identifying every energy source, moving air included, shutting down and isolating, one personal lock per worker, releasing stored energy, and trying to start the unit before the door is opened.