The sequence of operation decides what a cleanroom does on restart, on a trip and in a power cut. QA usually meets it at OQ, when every change costs a software revision and a retest. Walk it line by line with QA and maintenance before panels are built: start order, trips, alarm delays and fail positions.
Cooling coils foul on the air-entering face, while water and growth appear on the leaving side over the drain pan. A hygienic AHU needs access sections upstream and downstream of the coil and a sloped, reachable drain pan that extends past the leaving face.
A pass box sits across a grade boundary designed for at least 10 Pa. The interlock does not fix a worn door seal, a static box is made safe by the disinfectant contact time rather than by waiting, and a dynamic box needs its supply balanced against both rooms and its HEPA filter leak tested.
Clean AHU cooling coils from the leaving face with low-pressure water or steam and an approved, fully rinsed detergent, after checking the drain. Take the frequency from the coil's pressure drop trend against a commissioning baseline, and record the method, detergent batch, before and after readings and photos of both faces.
Warranty terms usually decide which chiller and AHU work goes to the OEM, and the split is rarely revisited. Keep compressor, refrigerant and firmware work with the OEM, bring filters, cleaning, trending and first response in-house, and file every service report in the site CMMS under change control.
The pressure drop at which a supply AHU's final filters are changed should be the dirty-filter allowance the fan was selected for at design stage, checked at FAT and quoted in the maintenance task. Raise it later and room pressure drifts down inside its alarm band, visible only on the trend.
A pre-filter changed at 150 Pa on a 0–1,000 Pa gauge sits in the bottom 15% of the dial with about 20 Pa of uncertainty. A 0–250 Pa gauge puts it at 60% with 5 Pa. Range each stage's gauge and transmitter to its own change point.
A V-belt sheds rubber dust into the airstream for its whole life, and in a GMP supply AHU that dust loads the final filters. Belt drives also lose a few per cent of shaft power and need regular tensioning. Direct-drive plug fans avoid all three, though a large belt-driven housed fan can still win at high pressure.
A pressure gauge shows filter loading but not a collapsed bag, a slipped gasket or a wet drain pan. Viewing windows and internal lights in the filter, coil, humidifier and fan sections let technicians check with the unit running. Double-glaze windows on cold sections, and keep the doors for checks that need a stop.
UV-C lamps limit microbial growth on the coil surfaces the light reaches. They do not remove dust or scale from the fin pack, and lamp output falls with running hours. After fitting them, keep coil inspection and cleaning in the maintenance plan and add lamp hours, a replacement date and an interlock test.