Each cleanroom luminaire breaks the ceiling's pressure boundary, and whether it is serviced from the room or the void drives most of the specification. Ask for a flush, gasketed face and chemical resistance data for your disinfectants, leave the ceiling to the filters in unidirectional airflow, and set illuminance from the task with EN 12464-1.
Airlock door interlocks protect a 10–15 Pa step between grades; a fire needs the doors to open. Specify both together: interlock logic, status lamps, fire-alarm release, fail-safe locks, a logged BMS alarm on every override, and a release tested at FAT, at OQ and periodically.
The installed HEPA scan covers media, frame and the filter-to-housing seal, but not the flange between housing and ceiling. Where the ceiling void runs at higher pressure than the room, unfiltered air enters there. Seal it with an evenly compressed gasket and sealant bead, then probe the flange and file the result.
An FFU array can average 0.45 m/s and still have a corner at 0.30 m/s. Measure each unit on a grid at FAT with fan speed settings recorded, then repeat the grid across the installed array at OQ. A flat map is healthy; a low edge points at speed, plenum, blanking or lights.
Air through a 25% open floor panel moves 4 times faster than the downflow above it, and that pressure drop keeps a fab bay's airflow vertical. Use less open area near return chases, solid panels under tools with rebalancing around them, sealed cut-outs, and check with a smoke study after tool install.
An air shower blows loose fibres off the outside of a coverall and interlocks two doors. It does nothing about what operators shed from underneath. It earns its place at powder-area entries and interlocked routes, and it should never be the reason a gowning step disappears from the procedure.
A pass box exists for its interlock: one door stays locked until the other is shut. Each side needs an indicator showing why, a dynamic box should show when purge time has run, and the locks' behaviour on power failure must be decided in the risk assessment and tested at OQ.
A cleanroom door that opens towards the lower pressure is pushed off its seal: 15 Pa on a 0.9 m by 2.1 m leaf is about 28 N. WHO's HVAC guideline says swing doors should normally open to the high-pressure side. Where escape rules differ, choose the closer for the pressure and justify the exception.
A wrong fan duty found at FAT means a revised test sheet; found on a live site it can mean a crane and a delayed OQ. A useful hygienic AHU FAT checks dimensions, casing leakage, fan duty, filter seals, control I/O and material records. Every AeroSano unit is FAT-tested and witnessed, with its equipment file compiled during production.