The HEPA housing joint the filter scan misses

The installed HEPA scan covers media, frame and the filter-to-housing seal, but not the flange between housing and ceiling. Where the ceiling void runs at higher pressure than the room, unfiltered air enters there. Seal it with an evenly compressed gasket and sealant bead, then probe the flange and file the result.

InsightRead

An FFU array can average 0.45 m/s and still have a corner at 0.30 m/s. Measure each unit on a grid at FAT with fan speed settings recorded, then repeat the grid across the installed array at OQ. A flat map is healthy; a low edge points at speed, plenum, blanking or lights.

InsightRead

Raised-floor panels and downflow in a fab bay

Air through a 25% open floor panel moves 4 times faster than the downflow above it, and that pressure drop keeps a fab bay's airflow vertical. Use less open area near return chases, solid panels under tools with rebalancing around them, sealed cut-outs, and check with a smoke study after tool install.

InsightRead

An air shower blows loose fibres off the outside of a coverall and interlocks two doors. It does nothing about what operators shed from underneath. It earns its place at powder-area entries and interlocked routes, and it should never be the reason a gowning step disappears from the procedure.

InsightRead

Door swing and the pressure cascade

A cleanroom door that opens towards the lower pressure is pushed off its seal: 15 Pa on a 0.9 m by 2.1 m leaf is about 28 N. WHO's HVAC guideline says swing doors should normally open to the high-pressure side. Where escape rules differ, choose the closer for the pressure and justify the exception.

InsightRead

What a useful AHU factory acceptance test checks

A wrong fan duty found at FAT means a revised test sheet; found on a live site it can mean a crane and a delayed OQ. A useful hygienic AHU FAT checks dimensions, casing leakage, fan duty, filter seals, control I/O and material records. Every AeroSano unit is FAT-tested and witnessed, with its equipment file compiled during production.

Read