A change is closed by data, not by installation

ICH Q10 expects changes to be evaluated after implementation. Closing a change the day the part is installed skips that step. Define the effectiveness check when the change is approved: the data that shows the objective was met, a period long enough to include the original conditions, and the result that closes it.

InsightRead

What a supply-duct RH sensor is good for

Air leaving a coil at 12 °C and 95% RH reads about 50% RH at 22 °C with the same 8.3 g/kg of water. A duct RH sensor after the coil works at the top of its scale. Control the coil on dew point or leaving-air temperature, and keep duct RH after reheat as a wet-filter alarm.

InsightRead