When a supply AHU trips with extract fans running and dampers open, a Grade B room loses its 10–15 Pa margin and pulls air from the lower grade. Tight-shutoff dampers with a tested leakage class, defined fail positions, interlocks, proven position and a supply-first restart keep the cascade, and a deliberate fan trip at FAT proves it.
A 0–10 V transmitter where the IO list says 4–20 mA passes a visual FAT and fails on site. That and four more defects (missing tags, gasket gaps, drain pans that hold water, missing documents) are worth checking at every AHU FAT against the approved specification and IO list.
On the suction side of the fan, any casing leak between the final filter and the fan draws unfiltered plant-room air into the supply. On the pressure side leaks blow outward and the filter catches what the fan sheds. The cost is a plenum, and the filter bypass class still needs specifying in either layout.
An AHU condensate line piped directly into a floor drain gives backed-up water and sewer gas a route to the unit. Each AHU needs its own trap, then a visible air break into a tundish or trapped gully, sized to the local plumbing code. The gap also shows anyone passing whether condensate is running.
A pressure gauge shows filter loading but not a collapsed bag, a slipped gasket or a wet drain pan. Viewing windows and internal lights in the filter, coil, humidifier and fan sections let technicians check with the unit running. Double-glaze windows on cold sections, and keep the doors for checks that need a stop.
Most first-start damage to an AHU comes from something left inside or left bolted. Remove transit fixings, test insulation, bump the fan for rotation, run at low speed, then read current, vibration and bearing temperature before ramping to duty and recording the static pressure profile as the baseline.
Default drive parameters will run an AHU fan but may not restart it after a power dip. Set the motor nameplate data, run the motor identification, set speed limits and ramps, add skip bands where the unit resonates, then decide and test behaviour on power loss, signal loss and fire mode. File the parameter list.
A locked isolator does not stop a fan that windmills in the draught from a neighbouring unit. Isolating an AHU means identifying every energy source, moving air included, shutting down and isolating, one personal lock per worker, releasing stored energy, and trying to start the unit before the door is opened.
An electric heater in an AHU overheats when airflow stops. At the factory test, witness each link of its safety chain: the airflow interlock, the automatic-reset and manual-reset high-limit cut-outs, the fan run-on, the clearance to filters and sensors, and a contactor that can cut power if the solid-state relay fails conducting.
An AHF injects the opposite of the harmonic current its CTs measure, so CT position decides what it corrects. Put CTs on the fan-wall feeder, match source- or load-side CTs to the filter setting, and choose between a filter at each AHU and one at the main board before ordering.
EC fan drives without a DC choke typically draw 65–75% THDi; with one, 35–42%. Humiley's design target is 5% or less at the point of common coupling; IEEE 519-2022 limits TDD by short-circuit ratio. In a fan wall, identical units add up, so request harmonic data and a harmonic study at design stage.
A wrong fan duty found at FAT means a revised test sheet; found on a live site it can mean a crane and a delayed OQ. A useful hygienic AHU FAT checks dimensions, casing leakage, fan duty, filter seals, control I/O and material records. Every AeroSano unit is FAT-tested and witnessed, with its equipment file compiled during production.