Cooling towers in the tropics: wet-bulb sets the floor

Cooling tower leaving water equals wet-bulb plus approach, and each kelvin of condenser water costs compressor power. At a 2–3% per kelvin rule of thumb, one extra kelvin of approach on a chiller drawing 180 kW is about 4.5 kW, or roughly 36,000 kWh over 8,000 running hours.

InsightRead

At a 6 K difference each kW of cooling needs about 0.14 m³/h of chilled water, so 500 kW moves about 72 m³/h. When return water falls to 10 °C the same load needs 50% more water and, on a fixed system, about 3.4 times the pump power. Two-way valves and a watched return temperature protect the design difference.