Under EU GMP Annex 1 (2022), the Contamination Control Strategy has to connect barriers, airflow, personnel and material flows, cleaning, utilities and monitoring. A useful test for any CCS: every line should point to a drawing, calculation or test, not to a procedure written after construction.
EN 1886 class L1 limits casing leakage to 0.15 l/s per m² at −400 Pa; L2 allows about three times more. As filters load and casing pressure rises, leakage grows, room offsets shrink and pressure control hunts. Specify L1, filter bypass F9 and a witnessed leakage test at FAT.
An AHU qualified in Ho Chi Minh City's dry season has not met its design weather. On a wet afternoon, holding 21 °C and 45% RH needs air off the coil at a dew point of about 8.5 °C or a little below. Size fresh-air coils on peak dew point and keep humidity monitoring running through the first wet season.
Designer, supplier, contractor and maintenance team each hold part of a facility's design intent, and assumptions get lost at every boundary. Humiley works as four divisions on one design basis, so the drawing, the factory acceptance test and the maintenance plan all trace back to the same requirements.
Welcome to Humiley Group INC. Our office is more than a workplace; it is a strategic center dedicated to delivering excellence for the Life Sciences and High-Tech sectors.
As we stand at the threshold of 2022, Humiley Group INC takes this moment to reflect on our journey and the steadfast values that guide our work in the pharmaceutical and semiconductor sectors. We begin this new year with a renewed pledge…
For decades, IT (Information Technology) and OT (Operational Technology) existed as two parallel worlds within an enterprise — IT managed data, emails, office software, and network security; OT managed machinery, production lines,…
Precision in Practice: 3D Design in Pharmaceutical Projects. In pharmaceutical projects, 3D design is more than visualization — it is a foundation of compliance. In GMP-regulated environments, design decisions directly affect safety,…
In pharmaceutical facilities, contamination control is not defined by room classification alone — it is defined by how flows interact. Even a facility that meets cleanroom classification requirements can face GMP risks if critical flows…
Beyond the Alarm: Why Integrated Fire, CCTV & Public Address Systems Are the Future of Enterprise Security. Have you ever wondered: "What happens when a fire alarm goes off at 2:00 AM in an empty warehouse or office?" In…
A cleanroom can meet its classification on paper, yet fail GMP expectations if HVAC performance is unstable or poorly aligned with operational reality. Cleanroom performance is often discussed in terms of ISO classes or GMP grades.
In pharmaceutical facility design, if the HVAC system is the "lungs," then the Zoning and Pressure Cascade strategy is the "immune system." It creates invisible but effective barriers that prevent microbial ingress and strictly control…