When cooling and reheat valves open together at 20 ± 0.5 °C, the cause is usually a zero gap between the two control sequences. Check the trend first. Where the product data supports 20 ± 2 °C, cooling above 21 °C and reheat below 19 °C let the room drift between with both valves shut.
Ten per cent on the load, on the airflow and on the coil multiplies to 1.33, because each margin sits on the one before. The oversized coil runs at part load most of the year, condenses less water, and RH climbs while temperature holds. One named margin and a part-load check avoid it.
A single dew-point reading in the return duct says little about a dry room. Qualification should map dew point at working height, time the recovery after an airlock door opening, leak-test the envelope and use sensors calibrated at the dry end, with limits set from what the cell chemistry tolerates.
A tropical shower can drop outdoor air from 32 °C to about 26 °C while it still holds around 21 g/kg. The fresh-air coil loses sensible duty but keeps all its latent duty, and the room's own heat does not change. A single coil on temperature control closes and room RH climbs.
Heat of adsorption and carry-over from the regeneration sector warm the air leaving a desiccant rotor. Size the post-cooler on rotor leaving temperature at full duty, treat it as a dry sensible coil, control room temperature on it and humidity on the rotor, and check the chilled water it needs.
In a staged system only the fresh air is drier than the room. With 220 W of latent gain and 300 L/s of fresh air it must arrive about 0.24 g/kg drier; at 150 L/s, 0.49 g/kg. Check humidity before cutting outdoor air for energy.
A room at 24 °C and 55% RH reads about 62% RH at 22 °C if no water is removed, because the dew point has not moved. On most cleanroom air handling units a lower setpoint only cuts reheat. Compare supply air dew point with room dew point before changing anything.
Reheat lowers the RH reading and leaves the water in the air. Before adding it, check outdoor dew point against design, chilled water temperature and valve position, and coil leaving dew point. Then look at reheat and the room sensor, and finally at doors, infiltration and new moisture sources.
An ISO 8573-1:2010 class such as [1:2:1] is three limits in a fixed order: particles, water as pressure dew point, and total oil. Class 2 water is −40 °C or lower; class 1 oil is 0.01 mg/m³ or less. The class does not name a location, so state the point of use.
On the first pull-down a dry room's dew point falls quickly and then flattens above the target. Seal and leak-check first, run the room empty, and plot dew point at supply and return. A level line points to a leak; a line still creeping down points to wet materials. People and doors come last.
Below 0 °C, moisture in air can be stated as a dew point over supercooled water or a frost point over ice, and the frost point is the warmer number. At a frost point of −40 °C the dew point is about −43.7 °C. A dry-room specification should say which one it means.
Some reheat is the price of dehumidification; the rest is waste. Five BMS trends separate the two: cooling and reheat valve positions together, supply dew point against what the rooms need, overlapping setpoints, temperature change across a coil with its valve shut, and the same pattern at night and weekends.