Receiving HEPA filters: what to check before fitting

A HEPA filter leaves the factory tested, then travels by container, forklift and scaffold. Check the cartons on arrival, match label class, serial number and rated airflow to the schedule and test report, store dry within the stacking mark, open only at a clean work area and inspect media and gasket under strong light before fitting.

InsightRead

0.5%: the repair allowance EN 1822-4:2009 gave a new HEPA filter

EN 1822-4:2009, since replaced by EN ISO 29463-4, allowed a HEPA filter to be repaired and retested: all repairs together, whoever made them, up to 0.5% of the face area, none longer than 3.0 cm, unless buyer and seller agreed otherwise. Most purchase orders are silent. State whether repairs are accepted and have each one marked on the scan report.

InsightRead

Why cleanroom airflow is called unidirectional

At 0.45 m/s across a 1 m clean zone the Reynolds number is about 30,000, far beyond laminar flow. ISO 14644-1 and the 2022 EU GMP Annex 1 use the term unidirectional airflow: steady velocity, roughly parallel streams. It is tested by air speed, uniformity and smoke studies, so write it that way in the URS.

InsightRead

EU GMP Annex 1 (2022) asks for an integrity test of final filters at requalification and puts no age on the filter. A terminal HEPA is replaced when a leak cannot be repaired within site limits, when pressure drop reaches the manufacturer's final value, or after damage or wetting. On glass-fibre media, dust loading alone does not lower efficiency.

InsightRead

Replacing one failed terminal HEPA in a live Grade C suite starts with change control and an equivalent filter. Stop work, bag the old filter, inspect the housing, then fit and leak-scan the new filter in place. Clean and check airflow, pressures, counts and recovery before release, with the scope agreed in the change record.

InsightRead

In a fab, the yield report is the slowest sensor

Filtration, AMC control, ±2% RH micro-environments and UHP utilities can each drift without an alarm. Designing facility monitoring with them, measuring at the tool, trending utilities and power on one time base and setting alert limits inside action limits, shows drift before the yield report does.

Read

EN 1822 rates H13 at 99.95% and H14 at 99.995% efficiency at MPPS. H14 earns its cost over open product in Grade A and on scan-tested terminal filters. In well pre-filtered Grade C and D rooms, H13 usually suffices, and a poor seal defeats either class.

Read