ISO 13485 §6.4.2 asks for documented contamination control without naming a cleanroom class. Setting the class from sterilisation method, patient contact and bioburden sensitivity often lands device assembly at ISO 8, with ISO 7 only where needed, less air than Grade C, a smaller AHU and a reason an auditor can read.
In tall rack storage, a fire low in the rack climbs the flue spaces while standard-spray ceiling sprinklers open late and struggle to reach it. At 7.5 m top of storage, unless an ESFR design covers the commodity, in-rack sprinklers with rack and sprinkler layouts fixed together protect both the building and the supply chain.
Grade, temperature and humidity ranges, pressure to each neighbour, internal loads and finishes all change airflow and equipment. Agreeing a Room Data Sheet per room before layout drawings start, starting from a library of 34 standard pharma RDS, avoids redoing load calculations and AHU selections later.
High-purity PVDF joined like ordinary plastic pipe leaves fusion beads that trap bacteria, so fab UPW loops use bead-and-crevice-free joints. UHP gas lines add electropolished 316L, orbital welds with coupons, helium leak tests and outlet particle, moisture and oxygen checks. Pharma WFI practice shares much of the discipline.
A room data sheet begins as a design input that changes weekly and ends as the qualified record behind OQ, PQ and monitoring limits. Each role needs different revision control. Agree the freeze point before DQ, so design and QA are never editing different versions of the same room.
In a Li-ion dry room at −60 °C dew point and below, extra air changes do not help: return air often passes back through the desiccant rotor, so more supply air means a bigger rotor and more regeneration heat. Size airflow from the moisture balance; pressure control, airlocks and envelope sealing carry over from pharma.
WHO guidance describes three phases for water system qualification: at least 2 weeks of intensive sampling, a second phase under the approved SOPs, then a full year to capture seasonal change. Sampling points, lab capacity and trending need planning for the whole year.
ISO Class 1 allows 10 particles of 0.1 µm and larger per cubic metre; ISO 5 allows 100,000 at that size. At that level the installed leak scan must prove frames and grid, not just the U15 filter, single-digit counts need large sample volumes, and airborne molecular contamination needs its own sampling plan.
A room's pressure differential sits on the room data sheet as a design value and in the monitoring SOP as alarm limits, often written months apart. Before OQ, list every door with the RDS revision it was balanced to and the current SOP alarm limits, and close each row that disagrees.
EN 1822 ULPA classes add a nine each above H14: U15 99.9995%, U16 99.99995%, U17 99.999995% at MPPS. Semiconductor ISO Class 1 to 3 spaces need them. A pharma Grade A zone at ISO 5 rarely does, because people and seal leaks drive its counts; H14 with a sound seal usually carries it.
Tropical GMP HVAC cools to dehumidify and then reheats, all year. A heat recovery chiller sends condenser heat to the reheat coils: 1,000 kW of cooling at COP 5 rejects about 1,200 kW. Condensing at 50 °C instead of 37 °C cuts ideal COP by about 30%, so it suits steady reheat.
Lactose, starch and microcrystalline cellulose are combustible dusts, and the granulation dust collector is one of the places that concentrates them. Test the blend for explosibility first, protect with venting, flameless venting or suppression plus inlet isolation, site the collector where a vent can discharge safely, then choose cartridge or bag media.