Company news from Humiley Group INC and technical notes on cleanroom HVAC, GMP validation, semiconductor environments and energy-storage engineering.

  • 780 articles

News

News

13 articles tagged #ISO14644.

A photometer leak scan passes a filter when downstream readings stay below 0.01% of the measured upstream concentration. At 20 µg/L upstream the threshold is 0.002 µg/L; a thin challenge pushes it toward the instrument's zero and a real leak reads clean. Reports should state the upstream figure per filter and where it was sampled.

InsightRead

16 sampling locations where there used to be 10

ISO 14644-1:2015 replaced the square-root rule for classification sampling locations with Table A.1. A 100 m² room went from 10 locations to 16. The revision also dropped the 95% UCL calculation and asks for one location per section of equal area. Requalification plans written before 2016 should be checked against the table.

InsightRead

A filter specification tenders can compare

Write "high-efficiency filtration" and three vendors can price three different filters. "H14 to EN 1822, installed leak test to ISO 14644-3" fixes the filter by a lab test at MPPS and the installed condition by an aerosol scan in the room. The housing then needs its own line, so the scan is physically possible.

InsightRead

Cleanroom setback: timer or particle counts

A timed airflow setback is simple to validate but blind to off-schedule activity. Particle-count-driven airflow follows real use and can save more, but counters and their failure modes join the validated system. Either way, the room must recover to its at-rest limits, pressures stable, before operations restart.

InsightRead

Cleanroom OQ tests depend on each other. Measure airflow first, then pressure differences, then the installed filter leak test, then airflow visualization, and finish with classification and recovery. A particle count taken before the leak test may have to be repeated once a filter is repaired.

InsightRead

Open ductwork on site and short-lived terminal HEPAs

Construction dust left in supply ducts ends up in the terminal HEPA filters, which then load in months. Order ductwork factory-cleaned and capped, store it off the floor, re-cap every open end at the end of each shift, inspect and wipe each section before connection, and fit the terminal filters last.

InsightRead

ISO 14644-3 lists eleven supporting cleanroom tests and gives a method for each, from air pressure difference to segregation. It says they may not all be required and that tests should be selected in a manner agreed between customer and supplier. The test specification has to name the tests, the occupancy state and the acceptance criterion before the work is priced.