Run-to-failure is a valid maintenance strategy only when a failure shows at once. Standby pumps, fire dampers and smoke detectors fail silently and never qualify. For the rest, check GMP impact, replacement cost and restore time, then record each decision in the criticality assessment with its reason.
A bound, signed paper logbook can meet ALCOA+, but it cannot link an entry to the work order, part and deviation. A GMP CMMS makes those links part of the record, provided it is validated to Annex 11 and 21 CFR Part 11 with real access control and an audit trail.
A single PM compliance percentage hides the overdue task QA cares about. Track PM compliance by criticality, overdue critical tasks listed by name, repeat failures on the same asset, and mean time to restore the pressure cascade from the BMS trend. All four need a CMMS asset register with criticality assessed.
A room held at 45% RH ±2% is really at 47% when its sensor has drifted 2% low, and the BMS still shows 45%. Tight bands need sensor accuracy and reference accuracy tighter than the band, calibration near the setpoint, evidence-based intervals and as-found records.
After an AHU failure, QA decides on product from one report. It needs a timeline built from BMS and EMS timestamps, trend exports for every affected room, the impact on rooms and batches, and a CAPA with owners and dates. All four can be drafted before the day shift starts.
Desiccant rotors lose capacity slowly: worn sector seals let wet air cross over, a slipping drive slows the rotor, dust and solvent vapour foul the media. Measuring outlet dew point, airflow and reactivation temperature against the commissioning record shows the trend before a −60 °C dry room does.
Critical spares sit for years before use. Store filters upright in their cartons and issue the oldest first, turn spare motor shafts at the manufacturer's interval, track shelf life on belts and seals, keep electronics dry in anti-static packaging, and label each item with the asset it fits.
O&M manuals are often accepted unread. Open the manual at one system you know and check that it describes the equipment as built, lists settings by tag, gives each maintenance task an interval and a method, lists spare parts with part numbers, and has fault-finding that starts from the symptom.
A work order closed with ticks holds no data. Rewrite each 'check' as a named measurement with its acceptable range and the action to take outside it, and record the as-found value before any adjustment. Start with the assets the criticality assessment ranks highest. The as-found figures become the trend.
Most of what a drive needs is on the motor rating plate. Read the voltage and connection against the supply, enter rated current, power, speed and power factor in the drive, check the IE efficiency class, the IP rating, insulation class and ambient, and copy bearing and regreasing data into the maintenance task.
The 2013 text of EU GMP Chapter 1 lists the qualification status of relevant equipment and utilities among the items a product quality review should include. Engineering can make that line believable with four more inputs: changes in the period, excursions and trends, calibration and maintenance failures with product impact, and the status of engineering CAPAs.
Capacitor makers publish a rule of thumb: each 10 K rise in operating temperature roughly halves the life of an electrolytic capacitor. A drive in a 45 °C plant room will not last like the same drive at 35 °C. Record the temperature inside the panel on every maintenance round, and ventilate or cool panels that stay hot.