Skip to content

Newsroom

News & Insights

Company news from Humiley Group INC and technical notes on cleanroom HVAC, GMP validation, semiconductor environments and energy-storage engineering.

  • 780 articles

Manufacturing & Distribution

Manufacturing & Distribution

53 articles tagged #Commissioning.

Pass boxes: where the grade boundary leaks

A pass box sits across a grade boundary designed for at least 10 Pa. The interlock does not fix a worn door seal, a static box is made safe by the disinfectant contact time rather than by waiting, and a dynamic box needs its supply balanced against both rooms and its HEPA filter leak tested.

InsightRead

Grade A is judged in operation

Grade A must meet ISO 5, 3,520 particles of 0.5 µm or larger per cubic metre, both at rest and in operation. An FFU array is therefore judged with operators and machines in the zone: uniform unidirectional flow, leak-tested H14 filters and a smoke study run with the real interventions.

InsightRead

Manufacturing & Distribution

H14 at 99.995%: only as good as its seal

An H14 filter passes 0.005% at MPPS in its factory test, H13 0.05%. A frame or gasket leak passing 0.05% of the airflow equals the whole H13 penetration, cancelling the upgrade. The installed leak test, scanning the filter face and perimeter seal, is where the real performance is proven.

InsightRead

What a pass box UV lamp does, and what it cannot

A pass box UV-C lamp doses only the surfaces it can see: 0.1 mW/cm² for 10 minutes gives 60 mJ/cm² on the tray top and nothing underneath. Output also falls with lamp age. Keep the disinfectant wipe as the validated step and manage the lamp with an hour meter and irradiance checks.

InsightRead

Clean AHU cooling coils from the leaving face with low-pressure water or steam and an approved, fully rinsed detergent, after checking the drain. Take the frequency from the coil's pressure drop trend against a commissioning baseline, and record the method, detergent batch, before and after readings and photos of both faces.

InsightRead

What to prove at a control panel FAT

A control panel FAT is the last time every wire is reachable and the drawings are on the table. Use it for IEC 61439-1 routine verification, point-to-point I/O, interlocks, alarm texts and approved software versions. The same fault found during site loop checks costs a day instead of minutes.

InsightRead

Manufacturing & Distribution

Hygienic and commercial AHUs, side by side

Standing water under a cooling coil is the classic growth source in an AHU. A hygienic unit adds a drain pan that empties completely, smooth closed inner surfaces, full-size access doors, filter bypass class F9 to EN 1886, removable parts and a complete equipment file. Write each into the specification as a FAT check.

InsightRead