49 articles tagged #HumidityControl.

A 75% RH fixed point from table salt

A saturated sodium chloride slurry in a sealed container holds the air above it at about 75% RH at 25 °C; magnesium chloride gives about 33%. The two points show whether a humidity probe has drifted between calibrations. It is a field check and does not replace a traceable calibration.

InsightRead

Reheat lowers the RH reading and leaves the water in the air. Before adding it, check outdoor dew point against design, chilled water temperature and valve position, and coil leaving dew point. Then look at reheat and the room sensor, and finally at doors, infiltration and new moisture sources.

InsightRead

The ICH stability guideline sets the accelerated study at 40 °C ± 2 °C and 75% RH ± 5% RH for a minimum of 6 months. If long-term studies run at 25 °C/60% RH, a significant change there should be followed by intermediate testing. For the chamber, excursions beyond the tolerances for more than 24 hours should be described in the study report.

InsightRead

An action alarm set at the specification limit leaves no margin for the sensor's uncertainty, so the room may already be outside when it rings. Borrow the guard band from calibration practice: with a 60% RH limit and ±2% RH uncertainty, set the action alarm at 58%, add an alert before it, and record the reasoning with the calibration data.

InsightRead

ISO 14644-3 is a menu of tests, and someone has to order

ISO 14644-3 lists eleven supporting cleanroom tests and gives a method for each, from air pressure difference to segregation. It says they may not all be required and that tests should be selected in a manner agreed between customer and supplier. The test specification has to name the tests, the occupancy state and the acceptance criterion before the work is priced.