When cooling and reheat valves open together at 20 ± 0.5 °C, the cause is usually a zero gap between the two control sequences. Check the trend first. Where the product data supports 20 ± 2 °C, cooling above 21 °C and reheat below 19 °C let the room drift between with both valves shut.
A tropical shower can drop outdoor air from 32 °C to about 26 °C while it still holds around 21 g/kg. The fresh-air coil loses sensible duty but keeps all its latent duty, and the room's own heat does not change. A single coil on temperature control closes and room RH climbs.
In a staged system only the fresh air is drier than the room. With 220 W of latent gain and 300 L/s of fresh air it must arrive about 0.24 g/kg drier; at 150 L/s, 0.49 g/kg. Check humidity before cutting outdoor air for energy.
A room at 24 °C and 55% RH reads about 62% RH at 22 °C if no water is removed, because the dew point has not moved. On most cleanroom air handling units a lower setpoint only cuts reheat. Compare supply air dew point with room dew point before changing anything.
A saturated sodium chloride slurry in a sealed container holds the air above it at about 75% RH at 25 °C; magnesium chloride gives about 33%. The two points show whether a humidity probe has drifted between calibrations. It is a field check and does not replace a traceable calibration.
Reheat lowers the RH reading and leaves the water in the air. Before adding it, check outdoor dew point against design, chilled water temperature and valve position, and coil leaving dew point. Then look at reheat and the room sensor, and finally at doors, infiltration and new moisture sources.
The ICH stability guideline sets the accelerated study at 40 °C ± 2 °C and 75% RH ± 5% RH for a minimum of 6 months. If long-term studies run at 25 °C/60% RH, a significant change there should be followed by intermediate testing. For the chamber, excursions beyond the tolerances for more than 24 hours should be described in the study report.
An action alarm set at the specification limit leaves no margin for the sensor's uncertainty, so the room may already be outside when it rings. Borrow the guard band from calibration practice: with a 60% RH limit and ±2% RH uncertainty, set the action alarm at 58%, add an alert before it, and record the reasoning with the calibration data.
Below 0 °C, moisture in air can be stated as a dew point over supercooled water or a frost point over ice, and the frost point is the warmer number. At a frost point of −40 °C the dew point is about −43.7 °C. A dry-room specification should say which one it means.
Some reheat is the price of dehumidification; the rest is waste. Five BMS trends separate the two: cooling and reheat valve positions together, supply dew point against what the rooms need, overlapping setpoints, temperature change across a coil with its valve shut, and the same pattern at night and weekends.
A chilled-water reset driven by valve position alone can raise supply water by 2 K, save chiller energy in the dry season and leave dehumidifying coils unable to reach the dew point in the wet season. Lock the reset out on outdoor or supply-air dew point, retest it in the wet season and list the dehumidifying coils first.
ISO 14644-3 lists eleven supporting cleanroom tests and gives a method for each, from air pressure difference to segregation. It says they may not all be required and that tests should be selected in a manner agreed between customer and supplier. The test specification has to name the tests, the occupancy state and the acceptance criterion before the work is priced.