Company news from Humiley Group INC and technical notes on cleanroom HVAC, GMP validation, semiconductor environments and energy-storage engineering.

  • 780 articles

Life Sciences

Life Sciences

130 articles tagged #Validation.

GAMP 5 Second Edition puts critical thinking first

GAMP 5 Second Edition (2022) scales validation effort to risk to patient safety, product quality and data integrity, and adds agile and cloud guidance. On a GMP BMS, test alarms, audit trail and data transfer deeply. A quick check: count low-risk functions that still carry full test scripts.

InsightRead

E-signatures: the second signing is the test

21 CFR 11.200(a)(1) requires two distinct identification components for non-biometric signatures. Later signings in one continuous session must still use a component only the signer can execute, usually the password. Define the session and its timeout in writing, then test both cases at OQ.

InsightRead

CTD Module 3 describes the plant you are building

The CTD has five modules, and Module 3 (Quality) records the process, its controls and often the facility, including room grades, water grades and the conditions behind hold times. After approval, changing them generally needs a variation. Draft Module 3 and the design basis from one table and send every change to both teams.

InsightRead

Annex 1's scope reaches non-sterile plants

The scope of EU GMP Annex 1 (2022) says some of its principles, including the contamination control strategy, may be used for certain non-sterile products such as liquids, creams and ointments. A semi-solids plant that writes a CCS tying room grades, flows, water and monitoring to product risk has an answer for the inspector.

InsightRead

Keep the BMS outside the EMS validation boundary

When the BMS and the validated EMS share one platform, the validation boundary takes in the control logic and every setpoint change becomes change control. An EMS with its own sensors, database and QA alarms under Part 11 and Annex 11 allows the BMS to be managed under good engineering practice.

InsightRead

Annex 15: what packaging validation asks for

EU GMP Annex 15 gives packaging validation two paragraphs (section 7 of the 2015 text). Packaging equipment should be qualified, and primary packing equipment at the minimum and maximum operating ranges of its critical parameters, such as temperature, machine speed and sealing pressure. The qualified range belongs to a format, so a new pack size reopens it.

InsightRead

Engineering Solution & Consultancy

One more market is one more SKU to run

'Same product, new box' brings new artwork and codes to control, a registration that may need stability data at other climatic conditions, possibly a new pack to qualify, and one more changeover in the weekly plan. Cost the SKU as a small project before a launch date is promised.

InsightRead

Annex 11 and the BMS-to-EMS link

The 2011 text of Annex 11 (clause 5) says systems that exchange data electronically should include built-in checks for correct and secure entry and processing. On a BMS-to-EMS link we read that as status flags, a communication watchdog, end-to-end checks of units and time stamps, and a loss-of-communication test in the qualification.

InsightRead

Knowledge management in ICH Q10, in plain terms

ICH Q10 names knowledge management as one of two enablers of the pharmaceutical quality system: a systematic approach to acquiring, analysing, storing and disseminating information about products, processes and components. In a technology transfer, that means handing over the reason behind each parameter, along with the batch record.