Pass boxes: where the grade boundary leaks

A pass box sits across a grade boundary designed for at least 10 Pa. The interlock does not fix a worn door seal, a static box is made safe by the disinfectant contact time rather than by waiting, and a dynamic box needs its supply balanced against both rooms and its HEPA filter leak tested.

InsightRead

Grade A is judged in operation

Grade A must meet ISO 5, 3,520 particles of 0.5 µm or larger per cubic metre, both at rest and in operation. An FFU array is therefore judged with operators and machines in the zone: uniform unidirectional flow, leak-tested H14 filters and a smoke study run with the real interventions.

InsightRead

Manufacturing & Distribution

H14 at 99.995%: only as good as its seal

An H14 filter passes 0.005% at MPPS in its factory test, H13 0.05%. A frame or gasket leak passing 0.05% of the airflow equals the whole H13 penetration, cancelling the upgrade. The installed leak test, scanning the filter face and perimeter seal, is where the real performance is proven.

InsightRead

FFU filters: change from the room or from above

Either way an FFU filter is changed, the room stops for the room-side leak scan, cleaning and recovery. Top-side replacement needs a walkable ceiling and disturbs the plenum; room-side replacement brings the loaded filter out through the classified space. Both need upstream injection and sampling ports that can be reached.