Stack effect and the clean corridor

A 10 m stairwell at a 10 K temperature difference produces about 4 Pa of stack effect, and a door near the top or bottom can see up to half of it, a noticeable part of a 10–15 Pa cascade step. Shafts that open onto clean corridors make the cascade drift with floor, weather and door position.

InsightRead

Duct airtightness classes A to D each allow about a third of the leakage of the class before. At 400 Pa, 500 m² of class B ductwork may leak about 220 l/s, class C about 75 l/s. Leakage after the flow control point moves the pressure cascade without the controller noticing.

InsightRead

Hold cleanroom pressure on the extract side

A cleanroom is qualified on its supply airflow: air change rate, recovery time and hood velocity. Controlling room pressure by trimming supply moves those numbers with every door opening. Holding supply constant and modulating extract or return keeps the qualified airflow and still holds the pressure cascade.

InsightRead

For the same excess airflow, room pressure differential varies with the inverse square of the leakage area. On a finished cleanroom that area hides in door gaps, ungasketed light fittings, open socket boxes, panel joints and penetrations. Compare measured excess air with the design allowance at commissioning.

InsightRead

A dead sensor must look dead

Under NAMUR NE 43, a 4–20 mA loop is valid between 3.8 and 20.5 mA; 3.6 mA or below, or 21 mA or above, signals a fault. Configure the EMS to show those as bad quality and alarm, never the last good value, and detect stale values on digital links too.