Material airlock hold time: a dilution sum

At 20 air changes an hour, a material airlock needs about 14 minutes for a 100:1 particle drop after the outer door closes. The interlock needs a hold-open timer and alarm for trolleys, and the countdown should start at door closure. The gowning airlock is laid out around people instead.

InsightRead

What a supply-duct RH sensor is good for

Air leaving a coil at 12 °C and 95% RH reads about 50% RH at 22 °C with the same 8.3 g/kg of water. A duct RH sensor after the coil works at the top of its scale. Control the coil on dew point or leaving-air temperature, and keep duct RH after reheat as a wet-filter alarm.

InsightRead

Pressure taps and tubing that tell the truth

A 3 m/s supply jet near a pressure tap can shift the reading by up to about 5 Pa, down or up depending on its angle, which is a third to half of a 10–15 Pa cascade. Tap position, tubing without low loops, matched tube lengths and a still reference port decide whether a room pressure trend is trustworthy.

InsightRead

Cooling tower leaving water equals wet-bulb plus approach, and each kelvin of condenser water costs compressor power. At a 2–3% per kelvin rule of thumb, one extra kelvin of approach on a chiller drawing 180 kW is about 4.5 kW, or roughly 36,000 kWh over 8,000 running hours.

InsightRead