4:1: is the calibration good enough for the tolerance?

A ±1 Pa tolerance cannot be confirmed with a ±1 Pa reference. The common rule is a test uncertainty ratio of 4:1, so the calibration needs an uncertainty of ±0.25 Pa or better and the reference has to be better still. Where that cannot be met, state the uncertainty and apply a guard band. Check it on the certificate.

InsightRead

In ISO and IEC standards, shall states a requirement, should a recommendation, may a permission and can a possibility. Normative annexes bind; nothing in an informative annex, a note or an example has to be met to claim conformity. EU GMP is different: it is written in 'should' and still expected. Check the verb and the annex before quoting a clause.

InsightRead

What a harmonic study contains

A harmonic study has five parts: the single-line diagram and fault level at the point of common coupling, the harmonic spectra of the non-linear loads, a measurement of existing distortion, a network model compared with voltage and TDD limits, and a measurement after the mitigation is installed.

InsightRead

A 75% RH fixed point from table salt

A saturated sodium chloride slurry in a sealed container holds the air above it at about 75% RH at 25 °C; magnesium chloride gives about 33%. The two points show whether a humidity probe has drifted between calibrations. It is a field check and does not replace a traceable calibration.