A replacement AHU supplying 5% more air, with a flow-controlled return and door gaps leaking roughly as ΔP^0.65, takes a door from 10 Pa to about 19 Pa. Fixed dampers and shared AHUs soften that, but requalification scope stays a change control decision: IQ always, OQ on the cascade, reasons recorded for any stage skipped.
Cleanroom load calculations fail on their inputs: nameplate equipment heat, table lighting density, office-level occupancy, missing process heat and forgotten fan heat, about 2 K at 1,500 Pa. Vendor heat-release data, the lighting design and the process description give better numbers than any default.
Before the supply fan is selected, check whether the coil sheet quotes a wet or a dry air pressure drop, and read it with the entering condition: dry- and wet-bulb at the peak dew point case. Then check leaving dew point against room RH, face velocity below about 2.5 m/s and a realistic chilled-water ΔT.
5,500 CFM at 250 Pa is about 9,345 m³/h, 6.6% short of a 10,000 m³/h schedule at 400 Pa, and a 20 air-change room gets about 18.7. The static pressure gap shows only on the fan curve, and speeding the fan up for 7% more air costs about 23% more fan power.
Drying 10,000 m³/h of wet-season air from a 26 °C to a 9 °C dew point removes about 170 kg of water an hour, roughly 4 m³ a day at full load. The condensate is low in minerals and a candidate for reuse such as cooling tower make-up, after a site assessment.
Shrink an AHU cross-section by 10% and the air moves about 11% faster, while pressure drop across the coil and dampers rises about 23%. At 10,000 m³/h that is roughly 0.4 kW, about 3,800 kWh a year. Ask bidders for coil face velocity and the EN 13053 velocity class.
Air leaving a cooling coil stops short of the apparatus dew point by the bypass factor. With a 7 °C ADP, a bypass factor of 0.1 and 26 °C, 12 g/kg entering air, the leaving dew point is near 8.3 °C. Size the coil backwards from the dew point the supply air needs.
Standing condensate in an AHU drain pan sits upstream of the final filters. ASHRAE 62.1 asks for a pan sloped at least 10 mm per metre toward the outlet so it drains completely. Check the slope with a level at FAT, prime the trap after long shutdowns and inspect the pan on a schedule.
A 7.5 kW fan shaft load running 8,760 hours a year draws about 0.27 kW more at 90% motor efficiency than at 93%, roughly 2,350 kWh a year from one motor. Ask for tested motor-plus-drive efficiency at the duty point, because the IE class is rated at full load.
Long-lead AHUs are often ordered before a single end-of-design DQ report is signed, so a casing leakage class of L2 against a URS that asked for L1 surfaces at IQ as a deviation. Splitting DQ along the procurement packages, with each section signed before its order is released, finds it while the order can still change.
During start and stop, whichever fan moves first decides which way air flows through the door gaps. Positive suites start supply first and stop extract first; containment suites do the opposite. Interlock the order, define the response to a single fan trip and test it at OQ with a real power cut.
EU GMP Annex 15 allows some FAT results to be used at IQ and OQ when transport and installation do not affect them. For an AHU that means listing what the trip can change, from fan alignment to software version, retesting those on site and referencing the rest.