A desiccant dehumidifier selection depends on six inputs: fresh and return airflow, air condition after pre-cooling, target dew point, reactivation heat source, leakage allowance and redundancy. −40 °C dew point is about 0.08 g/kg and −60 °C under 0.01 g/kg, a step that can add a rotor stage.
A selection program will size a coil for any input, including a wrong one. Engineers who have worked the psychrometric chart by hand notice when an answer is off. Humiley's training pairs fundamentals with on-the-job work on real project packages, mentored by senior leads, starting from a 12-month internship.
Air leaving a cooling coil stops short of the apparatus dew point by the bypass factor. With a 7 °C ADP, a bypass factor of 0.1 and 26 °C, 12 g/kg entering air, the leaving dew point is near 8.3 °C. Size the coil backwards from the dew point the supply air needs.
After a cold spell in northern Viet Nam, warm humid air arrives while floors and stored goods are still cold. Air at 20 °C and 90% RH has a dew point of about 18.3 °C, so a 15 °C slab gets wet. Extra ventilation adds more of the same air; dry the air or warm the surface.
With the motor in the airstream, fan power becomes heat: about 2.1 K at 1,500 Pa and 60% efficiency, roughly 14 kW on a 20,000 m³/h unit. After the coil it reaches the room; counted twice, it oversizes a chilled-water coil that then dehumidifies poorly at part load.
ASHRAE 0.4%, 1% and 2% design conditions are exceeded about 35, 88 and 175 hours a year. For a room with a validated RH limit, choosing the percentile is choosing how many excursion hours you accept. Use the dehumidification dew point column, choose per room, and write the choice into the design basis.
Cooling coils pay for dehumidification in chiller kWh; desiccant rotors mostly in reactivation heat, often above 100 °C for silica gel rotors. Compare them by listing the heat the site already has and its temperature. Very low dew points need desiccant regardless, and rotor outlet air still needs cooling.
Humiley engineers have a web-based AHU selection platform with one psychrometric engine and an ErP compliance module, so a junior and a lead get the same coil from the same design point. Reviews can then question the inputs: the governing design condition, latent load, fresh-air fraction and the RH limit.
Water needs about 2,450 kJ/kg to evaporate, so every kg/h leaving a mopped floor or wash bay adds about 0.68 kW of latent load. It arrives after production, when the cooling coil unloads. Treat the cleaning shift as its own dehumidification design case.
An AHU design copied from Ho Chi Minh City to a site near Hanoi can miss the heating coil and the humidifier. Use ASHRAE's heating dry-bulb column to size preheat, the humidification dew point column to size the humidifier, and the dehumidification columns for the cooling coil.
Condensate leaving a fresh-air coil equals dry-air mass flow times the drop in humidity ratio. At 10,000 m³/h dried from 21 to 7 g/kg that is about 170 litres an hour. Timed at the trap on a humid day, a shortfall points at water temperature, flow or bypass.
Between 29 °C / 26 °C dew point outdoor air and 20 °C / 45% RH exhaust the enthalpy gap is about 47 kJ/kg. A 70% sensible exchanger recovers about 6.5 kJ/kg, 14%, and its supply side runs below the dew point, so it needs a drain. Most of the tropical load is moisture.