Nameplate kW is maximum electrical input. Heat released to a cleanroom depends on duty cycle, ducted exhaust, process cooling water and product. A 10 kW oven at 50% duty with half its heat ducted away adds about 2.5 kW. Summing nameplates oversizes coils and hurts dew point control at part load.
Recirculated cleanroom air returns near room condition and needs almost no dehumidification. In a worked wet-season example, 10,000 m³/h of fresh air costs about 186 kW of coil load. Remove avoidable fresh air from exhaust, leakage and over-pressurisation before investing in heat recovery devices.
Under EN 779, F9 was a filter class: 95% or more at 0.4 µm. Under EN 1886, F9 is a casing class: at most 0.5% of the airflow bypassing the filter frames. Specify filter stages to ISO 16890 or EN 1822 and the casing bypass class on its own line.
Tony Nguyen asks clients to test Humiley's younger engineers at design reviews with one question: what does the room do when the door opens? A Grade C room drawn 15 Pa above its corridor loses that difference with the door open. A good answer covers outflow through the doorway, the alarm delay and the recovery test.
When the fresh-air unit does all the drying and room AHU coils stay dry, every room's humidity depends on that one unit. Size its coil on the wet-season coincident condition, control on off-coil dew point, and decide in the design basis what happens when it trips.
Filter loading can swing AHU resistance from 250 Pa clean to 450 Pa at change-out while airflow must stay constant. Selecting near 350 Pa and checking design airflow at 450 Pa with the drive at full speed avoids both a fan stuck right of peak and an airflow shortfall. The energy difference is modest.
Mapping protocols from temperate countries ask for summer and winter studies. In southern Viet Nam the real extremes are the hot dry months, which test temperature, and the rainy season, which tests humidity and latent cooling load. Two mappings timed to the local calendar give an inspector a record worth reading.
A chilled-water valve with 10 kPa across it on a 40 kPa coil branch has an authority of 0.2. At part load it sits near its seat, hunts, and the cleanroom dew point swings. Size the valve drop close to the branch drop, aim near 0.5, and check the opening at minimum load.
Cleanroom load calculations fail on their inputs: nameplate equipment heat, table lighting density, office-level occupancy, missing process heat and forgotten fan heat, about 2 K at 1,500 Pa. Vendor heat-release data, the lighting design and the process description give better numbers than any default.
In a perfectly mixed room, a 100:1 particle reduction takes ln(100) = 4.6 air changes, about 13.8 minutes at 20 ACH. Real rooms take longer because mixing is imperfect. The ISO 14644-3 recovery test measures that gap, so predict it at design stage and fix diffuser and return positions early.
Bringing 10,000 m³/h of outdoor air from 29 °C / 26 °C dew point to 10 °C / 9 °C dew point takes about 186 kW of cooling, two-thirds of it condensing roughly 170 kg of water an hour. Fresh-air and exhaust quantities deserve the same scrutiny as filter grades.
When a chilled water plant designed for 5 K runs at 3 K, it needs about 67% more flow for the same load and stages chillers early. The usual causes are at the coils: three-way valves, fouling and low setpoints. Fix the coils and trend ΔT on the BMS.