Company news from Humiley Group INC and technical notes on cleanroom HVAC, GMP validation, semiconductor environments and energy-storage engineering.

  • 780 articles

Life Sciences

Life Sciences

379 articles filed under Life Sciences.

Grade B action limits and the alert levels below them

Annex 1 (2022) Table 6 sets Grade B maximum action limits: 10 CFU/m³ air, 5 CFU per settle plate over 4 hours, 5 per contact plate and 5 per glove print. Alert levels must sit below them and come from your own trend data, starting with a documented judgement in a new facility.

InsightRead

21 CFR 211.42 and 211.46 and EU GMP Chapter 3 ask for adequate ventilation, air control and filtration, but give no air change rate or pressure differential, and no filter class beyond HEPA for aseptic areas. Those come from Annex 1, FDA's 2004 aseptic guidance, ISO 14644 and the designer's justification, recorded in the design basis.

InsightRead

Pure steam quality is three tests, not one

EN 285 checks pure steam for dryness (at least 0.95, or 0.90 for metal loads), non-condensable gases (no more than 3.5%) and superheat (no more than 25 K). Each fails for a different piping cause: trapping and insulation, degassing and air ingress, or a large pressure drop near the point of use.

InsightRead

Pharma habits in a battery dry room

In a Li-ion dry room at −60 °C dew point and below, extra air changes do not help: return air often passes back through the desiccant rotor, so more supply air means a bigger rotor and more regeneration heat. Size airflow from the moisture balance; pressure control, airlocks and envelope sealing carry over from pharma.

InsightRead

When gowning fails, walk the change room

Annex 1 expects Grade A/B staff to be reassessed for gowning at least annually. When the same people keep failing, check the change room before retraining: a clear dirty/clean line, space to gown, stations in SOP order, and a final stage at the grade of the room it serves.

InsightRead

Read Annex 1 clause by clause before the inspection date

A Grade B room never retested for recovery after a ductwork change is an easy inspection finding, and six months earlier it is ordinary planned work. A written review reads Annex 1 clause by clause and gives each gap one row: clause, current state, risk, fix and rough size, finished before an inspection date is set.

InsightRead

Calendar PM vs criticality-based PM

Calendar maintenance gives every asset the same interval, so when hours run short the critical ones suffer with the rest. Scoring assets by the consequence of failure moves effort toward what holds a grade or a pressure cascade, and is best done once from the project's asset register.