A plant outside the EU earns an EU GMP certificate after an inspection by an EEA competent authority, usually triggered by the EU importer or MAH. Site Master File, inspection, graded deficiencies and a CAPA response come first; the certificate, or a non-compliance statement, then appears in EudraGMDP.
A Class II type B2 cabinet exhausts all of its air, so room supply must follow it on and off and the exhaust fan needs an alarm and interlock. An A2 exhausts around 30% and, on a canopy, barely moves the balance. Choose B2 only when volatile chemicals demand it.
In a GMP air handling unit, a wheel carries some exhaust into the supply by design, and a purge sector only reduces it. Run-around coils keep the streams apart at lower recovery. Plate exchangers leak in the direction the fan positions set, so mark and measure the pressure on each side before and at commissioning.
ISO 14644-1 allows a room to be classified as-built: installation complete, services running, no equipment, materials or people. On a new suite it shows whether the HVAC, filters and envelope can reach the class alone. It says nothing about machines or people, so the GMP classification is still done at rest and in operation.
In unidirectional airflow at 0.45 m/s, a 28.3 L/min particle counter needs an inlet about 37 mm across to sample isokinetically, and a 100 L/min counter about 69 mm. An undersized inlet draws air in too fast, large particles miss it by inertia, and the ≥5 µm count reads low.
Tropical GMP HVAC cools to dehumidify and then reheats, all year. A heat recovery chiller sends condenser heat to the reheat coils: 1,000 kW of cooling at COP 5 rejects about 1,200 kW. Condensing at 50 °C instead of 37 °C cuts ideal COP by about 30%, so it suits steady reheat.
A URS line such as at least 10 Pa above a Grade C corridor sets the airflow offset, the door leakage allowance, the pressure control range, the alarm limit and the OQ acceptance criterion, when the URS and validation strategy are written in parallel with the design.
AHRI's IPLV gives full-load efficiency a 1% weight, yet chiller offers lead with full-load COP. A 24/7 GMP plant in Viet Nam spends much of the year at part load, with condenser water warmer than the rating assumes. Ask for efficiency at each load point at your real condenser temperature.
Many potent suites recirculate through safe-change HEPA housings; where the risk assessment rules that out, every cubic metre is tropical outdoor air. Run-around coils recover heat with the airstreams fully separated, wheels open a leakage path, and dedicated fresh-air pre-cooling targets the latent load. Our energy modeling targets a 30% HVAC energy reduction.
Annex 1 (2022) expects an aseptic process simulation to imitate routine processing with worst-case conditions. An APS run right after a filter change and rebalance tests a different process. Schedule maintenance away from APS runs and record the HVAC state for each run like the interventions.
Two H14 filters from a new maker at 150 Pa initial pressure drop, fitted beside four originals at 110 Pa on one duct branch, take less air than their neighbours while the room total barely moves. Compare initial pressure drop before ordering, then change the whole set or retrim and measure every terminal.
On a 7.5 m rack, eye level is rarely the worst position. WHO mapping guidance expects loggers in three dimensions and at high-risk points: top racks under the roof, dock doors, cooling outlets and dead corners. The map then decides where the permanent monitoring probes belong.