ISO 16890 rates what a filter captures; Eurovent energy classes, A+ to E, compare what it costs to run at reference conditions. Two ePM1 70% filters 50 Pa apart in average pressure drop differ by about 2,000 kWh a year at 10,000 m³/h. Ask for the class and the pressure drop at your airflow.
MBH means thousands of Btu/h: 24 MBH is 24,000 Btu/h, about 7.0 kW. Entered as kW it oversizes the room about 3.4 times. Before converting, check whether the datasheet figure is electrical input or heat to the room, and keep the latent part for the moisture balance.
Shrinking a 10,000 m³/h duct from 700 × 500 mm to 600 × 400 mm raises velocity from about 8 to 12 m/s and velocity pressure from 38 to 80 Pa, so every fitting costs about twice. Set separate limits for mains and branches in the design basis.
A 10,000 m³/h fan at 1,500 Pa and 0.6 overall efficiency draws about 6.9 kW, around 61 MWh a year in a cleanroom. Every 100 Pa removed at design stage saves about 0.46 kW for the life of the plant. A pressure budget per AHU in the design basis is where it starts.
Raising a 6 × 5 m room from 3.0 m to 3.5 m drops 1,800 m³/h from 20 to 17.1 air changes. The in-operation particle count barely moves, because steady-state concentration depends on generation and supply airflow, not volume. Recovery takes about 17% longer. Restoring 20 ACH needs 2,100 m³/h.
A particle counter on UPS can stay powered through a power dip and count nothing if its vacuum pump sits on the normal supply. Network switches in risers, transmitters on AHU field panels and unsynchronised clocks leave the same kind of gap. Trace the supply of every item between the sensor and the historian.
A 3 m cleanroom at 100 W/m² and an 8 K supply difference needs about 12 ACH for cooling. If cleanliness sets 40 ACH, the other 28 are dilution air. Moving it through the central AHU costs fan energy; a recirculation loop or FFUs can move it at lower pressure.
Wind-driven rain past a plain louvre soaks the first filter stage of a fresh-air AHU. A 10,000 m³/h intake needs about 1.4 m² of louvre at 2.0 m/s, or 2.8 m² at 1.0 m/s, and the slower louvre admits less water. Add a drained plenum, a cleanable screen and an ISO Coarse first stage.
AHU quotations show price, rarely running cost. EN 13053 velocity, fan power and heat recovery classes, declared at design airflow, make offers comparable on energy. Without them the tender is judged on capital cost and the pressure drop of a small casing shows up later in fan energy.
A filter change record needs the isolation details, how the old filter was bagged, a frame and gasket check, ΔP before and after, and the leak-test decision. A terminal HEPA that is replaced or disturbed gets an installed leak test before the room returns to use.
Humiley engineers have a web-based AHU selection platform with one psychrometric engine and an ErP compliance module, so a junior and a lead get the same coil from the same design point. Reviews can then question the inputs: the governing design condition, latent load, fresh-air fraction and the RH limit.
An AHU design copied from Ho Chi Minh City to a site near Hanoi can miss the heating coil and the humidifier. Use ASHRAE's heating dry-bulb column to size preheat, the humidification dew point column to size the humidifier, and the dehumidification columns for the cooling coil.