Plot outdoor, mixed, coil-leaving, after-fan, after-reheat and room states on one psychrometric chart. A reviewer can see a mixed-air point off its line, a coil dew point without margin for the room latent load, over-drying paid for twice, and reheat oversized because fan heat was ignored.
Direct-on-line fans started together can ask a standby generator for six or more times their running current. Start fans through drives, restart in blocks a few seconds apart with controls on UPS and chillers last, and size the generator for its largest load step under ISO 8528-5.
When one location in a Grade C room recovers far slower than the rest, raising a 60 m³ room from 20 to 30 air changes adds 50% more air and may barely help. A smoke study usually shows short-circuiting to a return; moving or adding a low-level return is the cheaper fix.
"OK" on a FAT sheet records a judgement. "118 Pa, acceptance ≤ 150 Pa", with the gauge ID and calibration date, records a measurement that IQ, maintenance and an inspector can use years later, and shows when a pass was close. It is how the Excellence value looks on a test bench.
EN 1822 classes the filter, not the medium. PTFE membrane usually reaches a HEPA class at lower pressure drop and handles better than brittle glass fibre, but its surface catches oil aerosol from leak tests. Agree the test aerosol with the filter maker before specifying PTFE for pharma rooms.
A 100 cm² door gap at 15 Pa passes about 110 m³/h, but only doors on the suite boundary cost fresh air. Internal door leakage returns through the neighbouring room's grille. For twenty doors with four on the boundary, the leakage to make up is 440 m³/h rather than 2,200 m³/h of wet tropical air.
Reheat after a dehumidifying coil costs about 0.34 kW per 1,000 m³/h per kelvin, or 34 kW for 5 K on a 20,000 m³/h unit. Per kWh delivered, resistance and boilers cost most, heat pumps less, condenser recovery and wrap-around heat pipes least; tariffs and the site decide what fits.
Light office wear is about 0.5 clo, while full cleanroom gowning sits nearer 1.0 clo, and standing line work is about 1.6 met or more. Gowned operators are comfortable cooler than office staff, so set the room temperature in the URS with QA and EHS before the load calculation sizes the coil.
A full-size 592 × 592 mm bag filter is commonly rated at about 3,400 m³/h. A 20,000 m³/h AHU needs six frames; a casing with room for four runs each at 47% over, with higher pressure drop, possibly lower efficiency and fluttering pockets. The frame count belongs in the specification and the FAT.
Ten per cent on the load, on the airflow and on the coil multiplies to 1.33, because each margin sits on the one before. The oversized coil runs at part load most of the year, condenses less water, and RH climbs while temperature holds. One named margin and a part-load check avoid it.
An extra 100 Pa of filter resistance on a 10,000 m³/h supply costs about 460 W, roughly 4,000 kWh a year. The cheapest change point comes when the latest month's extra energy cost exceeds the average monthly cost since fitting, filter set included, provided it sits below the manufacturer's maximum final pressure drop.
A test at minimum fan speed with a door held open is OQ evidence; PQ shows normal operation, with production or a representative simulation, over a stated period. A step that forces a condition usually belongs in OQ, and separate protocols allow OQ to close before PQ starts.