The PIC/S GMP Guide and EU GMP are almost identical, revised Annex 1 included. In the EU the GMP principles are set in law and certificates sit in EudraGMDP; PIC/S authorities adopt the guide nationally and PIC/S certifies nothing. One design serves both; the EU inspection route is planned separately.
Put containment exhaust fans at the end of the run so ducts inside the building stay negative. Run duty and standby with isolation dampers and alarmed changeover, discharge vertically with height and velocity from a standard or a dispersion study, and keep the plume away from fresh-air intakes.
A 15–25 °C store in Viet Nam needs active cooling. Split units give cheap N+1 redundancy but a short air throw and little humidity control. A chilled-water AHU ducts air to the top of tall racking and can control dew point, with dearer redundancy. Humidity limits on the labels usually decide it.
Annex 1 expects the Contamination Control Strategy to be actively reviewed and updated. A yearly meeting catches changes late. Adding one question to every HVAC change control, EM adverse trend review and deviation closure form, asking whether the CCS still says the right thing, keeps it current with the site.
At a 6 K difference each kW of cooling needs about 0.14 m³/h of chilled water, so 500 kW moves about 72 m³/h. When return water falls to 10 °C the same load needs 50% more water and, on a fixed system, about 3.4 times the pump power. Two-way valves and a watched return temperature protect the design difference.
The CTD has five modules, and Module 3 (Quality) records the process, its controls and often the facility, including room grades, water grades and the conditions behind hold times. After approval, changing them generally needs a variation. Draft Module 3 and the design basis from one table and send every change to both teams.
The scope of EU GMP Annex 1 (2022) says some of its principles, including the contamination control strategy, may be used for certain non-sterile products such as liquids, creams and ointments. A semi-solids plant that writes a CCS tying room grades, flows, water and monitoring to product risk has an answer for the inspector.
When the HVAC load calculation assumes four operators and the aseptic process simulation qualifies six, the room runs outside its design basis. Write one maximum occupancy per room in the URS and carry it into the load calculation, room data sheet, APS protocol and entry SOP.
Under ASTM E2500, HVAC critical aspects should start from the product: its critical quality attributes, the process steps where the room can affect them, the room conditions at those steps, and a test for each. For a hygroscopic tablet that makes room RH critical, while the chiller and coil valve are commissioned under good engineering practice.
Before a product is transferred, compare what it needs with what the receiving facility has shown it can do: room grades and pressure cascade, containment, temperature and humidity from worst-month trend data, utility quality and capacity, and equipment principle and scale. WHO's guideline puts gap analysis among the first steps.
Good engineering practice is the design review, installation checks and commissioning that sit under qualification. WHO's HVAC guideline defines it, and EU GMP Annex 15 (2015) allows data from outside the manufacturer's own programs if justified and controlled. Commissioning sheets made with calibrated instruments and signed by the person who measured can then be relied on.
EU GMP Chapter 9, as it stands today, is one principle and three clauses. Listed areas should be examined to a pre-arranged program, by designated competent persons from the company working independently; every self inspection should be recorded, and so should the actions taken afterwards. The list of areas includes self inspection itself.