MPPS vs 0.3 µm: why EN 1822 and US HEPA ratings differ

EN 1822 rates HEPA filters at the most penetrating particle size, typically 0.1–0.25 µm for glass-fibre media, while US practice quotes 99.97% at a fixed 0.3 µm. Because 0.3 µm is above the MPPS, the two numbers come from different tests and cannot be compared line by line on a datasheet.

InsightRead

When 5% of a 10,000 m³/h, 12 °C supply leaks into a 32 °C ceiling void, about 3.4 kW of sensible cooling goes with it and the room is 500 m³/h short. A named airtightness class, a pressure test before insulation and sealed joints and access doors keep that cooling in the duct.

InsightRead

0.14 m³/h of chilled water per kW at a 6 K difference

At a 6 K difference each kW of cooling needs about 0.14 m³/h of chilled water, so 500 kW moves about 72 m³/h. When return water falls to 10 °C the same load needs 50% more water and, on a fixed system, about 3.4 times the pump power. Two-way valves and a watched return temperature protect the design difference.

InsightRead

A timed airflow setback is simple to validate but blind to off-schedule activity. Particle-count-driven airflow follows real use and can save more, but counters and their failure modes join the validated system. Either way, the room must recover to its at-rest limits, pressures stable, before operations restart.

InsightRead