A spring isolator with its transport bolt still fitted transmits everything. Remove transport locks, select isolators for the lowest drive speed, keep flexible connections slack, remove rigid bridges such as conduit or drain lines, use inertia bases where needed, and file the balance report and a vibration baseline.
An AHU's section split and weight are set by the tightest point on its delivery route: door clear openings, lift car and rated load, corridor corners, crane reach and floor loading. Survey the route before the general arrangement is frozen, and plan a casing leakage check after site reassembly.
A classified room's air change rate, recovery time and pressure steps were proved at one airflow. Constant volume holds each room's flow at that value with a terminal, while the fan speeds up as filters load. VAV moves supply with the cooling load, so it belongs in offices, technical areas and fume-hood exhaust.
Put containment exhaust fans at the end of the run so ducts inside the building stay negative. Run duty and standby with isolation dampers and alarmed changeover, discharge vertically with height and velocity from a standard or a dispersion study, and keep the plume away from fresh-air intakes.
A pre-filter changed at 150 Pa on a 0–1,000 Pa gauge sits in the bottom 15% of the dial with about 20 Pa of uncertainty. A 0–250 Pa gauge puts it at 60% with 5 Pa. Range each stage's gauge and transmitter to its own change point.
A 15–25 °C store in Viet Nam needs active cooling. Split units give cheap N+1 redundancy but a short air throw and little humidity control. A chilled-water AHU ducts air to the top of tall racking and can control dew point, with dearer redundancy. Humidity limits on the labels usually decide it.
A 100 cm² door gap at 15 Pa passes about 110 m³/h, but only doors on the suite boundary cost fresh air. Internal door leakage returns through the neighbouring room's grille. For twenty doors with four on the boundary, the leakage to make up is 440 m³/h rather than 2,200 m³/h of wet tropical air.
An AHU casing is described by five EN 1886 classes: strength D1–D3, leakage L1–L3, filter bypass up to F9, thermal transmittance T1–T5 and thermal bridging TB1–TB5. A witnessed FAT can test leakage on the real unit; transmittance and bridging come from a laboratory model box, so the model box report belongs with the offer.
A depyrogenation tunnel runs from the wash room into a Grade B filling room, across one or two grade steps, and releases heat next to the Grade A zone. Its own airflow balance and heat release per zone belong in the design basis, and the rooms are balanced with the tunnel at temperature.
Annex 1 expects the Contamination Control Strategy to be actively reviewed and updated. A yearly meeting catches changes late. Adding one question to every HVAC change control, EM adverse trend review and deviation closure form, asking whether the CCS still says the right thing, keeps it current with the site.
A V-belt sheds rubber dust into the airstream for its whole life, and in a GMP supply AHU that dust loads the final filters. Belt drives also lose a few per cent of shaft power and need regular tensioning. Direct-drive plug fans avoid all three, though a large belt-driven housed fan can still win at high pressure.
When a supply AHU trips with extract fans running and dampers open, a Grade B room loses its 10–15 Pa margin and pulls air from the lower grade. Tight-shutoff dampers with a tested leakage class, defined fail positions, interlocks, proven position and a supply-first restart keep the cascade, and a deliberate fan trip at FAT proves it.